V/Hz, Ω, Temperature, and A/Hz Measurements
5.1.2 Alternating Voltage Measurement with 1 MΩ Load Resistance
and Frequency Measurement with Selectable Low-Pass Filter
(METRAHITX-TRAOUTDOORTECHPRO only)
The measuring instrument includes a V
1MΩ
switch position for
electricians with an input resistance of approximately 1 MΩ.
Erroneous displays resulting from capacitive coupling during
voltage measurement in power supply systems are reduced to a
minimum in this way.
Note
METRAHITTECH: see note in chapter 5.1.1.
Ð In accordance with the voltage to be measured, turn the rotary
switch to V~
1MΩ
or .
Ð Connect the measurement cables as shown.
The “” connector jack should be grounded.
Voltage Measurement
Note
An intermittent acoustic signal warns the operator if the
measured value exceeds the upper range limit in the 1000 V
range.
Make sure that a current measuring range (“A”) has not been
activated when the multimeter is connected for voltage measure-
ment! If the fuse’s blowing limits are exceeded as a result of oper-
ator error, both the operator and the instrument are in danger!
Ð You can switch back and forth between voltage measurement
with and without low-pass filter.
Ð Press the FUNC | ENTER multifunction key repeatedly until unit of
measure V or V/Fil appears at the display.
Frequency Measurement
Ð Apply the measured quantity is the same way as for voltage
measurement.
Ð Manually select the measuring range for the voltage amplitude.
When the instrument is switched to frequency measurement,
the previously selected voltage measuring range remains
active.
Ð You can switch back and forth between frequency
measurement with and without low-pass filter.
Press the FUNC | ENTER multifunction key repeatedly until unit of
measure Hz or Hz/Fil appears at the display.
Lowest measurable frequencies and maximum allowable
voltages are included in chapter 8, “Technical Data”.
Measurement with Low-Pass Filter
Attention!
!
Be aware of the fact that dangerous voltage spikes are not
displayed during this type of measurement (see also “Voltage
Comparator”.
We recommend measuring voltage without the low-pass filter
first, in order to be able to detect any dangerous voltages.
A 1 kHz low-pass filter can be activated if required, in order to
filter out high frequency pulses of greater than 1 kHz, for example
when performing measurements at pulsed motor drives, i.e.
undesired voltages of greater than 1 kHz can be suppressed.
The active low-pass filter is indicated by the Fil display. The
multimeter is automatically switched to manual measuring range
selection.
1 kHz
28


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt SECULIFE HIT at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt SECULIFE HIT in the language / languages: English as an attachment in your email.

The manual is 0,93 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Gossen Metrawatt SECULIFE HIT

Gossen Metrawatt SECULIFE HIT User Manual - Dutch - 70 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info