GMC-I Messtechnik GmbH 27
Special Case: Suppressing Display of the Limit Value
The limit value cannot be
ascertained. The inspec-
tor is prompted to evalu-
ate the measured val-
ues himself, and to
acknowledge or reject
them with the help of the
softkeys.
Measurement passed:
key
Measurement failed: X
key
The measured value can
only be saved after it has
been evaluated.
8.3 Settings for Calculating Short-Circuit Current –
Parameter IK
Short-circuit current IK is used to test shutdown by means of an
overcurrent protective device. In order for an overcurrent protec-
tive device to be tripped on time, short-circuit current IK must be
greater than tripping current Ia (see table 6 in section 19.1). The
variants which can be selected with the “Limits” key have the fol-
lowing meanings:
IK: Ia The measured value displayed for IK is used without
any correction to calculate ZL-PE.
IK: Ia+Δ% The measured value displayed for ZL-PE is corrected
by an amount equal to the test instrument’s measuring
uncertainty in order to calculate IK.
IK: 2/3 Z In order to calculate IK, the measured value displayed
for ZL-PE is corrected by an amount corresponding to
all possible deviations (these are defined in detail by
VDE 0100-60 as Zs(m) 2/3 x U0/Ia).
IK: 3/4 Z Zs(m) 3/4 x U0/Ia
IK
Short-circuit current calculated by the instrument (at nominal voltage)
Z Fault loop impedance
Ia Tripping current (see data sheet for circuit breakers / fuses)
Δ
%
Test instrument inherent error
Special case: Ik > Ikmax, see page 28.
See page 28 on accessing the fuse table via the
HELP
key.
9 Measuring Line Impedance (ZL-N function)
Measuring Method (internal line resistance measurement)
Line impedance ZL-N is measured by means of the same method
used for loop impedance ZL-PE (see section 8 on page 25). How-
ever, the current loop is completed via neutral conductor N rather
than protective conductor PE as is the case with loop impedance
measurement.
Select the Measuring Function
Schuko Connection
(country specific)
Connection: 2-pole
Set Parameters
Press the softkey shown at the left in order to switch
back and forth between the country-specific measur-
ing adapter, e.g. PRO-Schuko measuring adapter
(Z503K) / 3-pole measurement and the KS-PROFIT-
EST INTRO (Z503L) for 2-pole measurement. The selected con-
nection type is displayed inversely (white on black).
Limit Value:
IK < limit value
LIMIT
ZL-N
Nom. current:
2 ... 160 A, 9999 A
Diameter: 1.5 to 70 sq. mm
Cable types: NY..., H07...
Number of wires:
1 to 10-strand
Tripping characteristics:
A, B/L, C/G, D, E, H, K, GL/GG & factor
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt Profitest Intro at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt Profitest Intro in the language / languages: English as an attachment in your email.

The manual is 1.69 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info