10.10 Earthing Resistance Measurement, Battery Powered – Ground Loop Measurement
(with current clamp sensor and transformer, plus PRO-RE/2 measuring adapter as accessory) (only MPRO & MXTRA)
2-Clamp Measuring Method
In the case of earthing sys-
tems which consist of sev-
eral earth electrodes (R1 ...
Rx) which are connected to
each other, earthing resis-
tance of a single electrode
(Rx) can be ascertained with
the help of 2 current clamps
without disconnecting Rx or
using spikes.
This measuring method is especially well suited for buildings or
systems for which probes and auxiliary earth electrodes cannot
be used, or where it’s impermissible to disconnect earth elec-
trodes.
Furthermore, this “spike-free” measurement is performed as one
of three measurements for lightning protection systems, in order
to determine whether or not current can be dissipated.
Figure at right:
PRO-RE/2 measuring adapter as
accessory for connecting the E-
Clip 2 generator current clamp
Connection
No probes or auxiliary earth electrodes are required.
The earth electrode is not disconnected.
Attach the
PRO-RE/2 adapter (Z501T)
to the test plug.
Connect the E-Clip 2 generator clamp (current clamp transformer)
via the 4 mm safety plugs at the PRO-RE/2 adapter.
Connect the Z3512A current clamp sensor to jacks 15 and 16 at
the test instrument.
Attach the 2 clamps to an earth electrode (earth spike) at dif-
ferent heights with a clearance of at least 30 cm.
Select Measuring Function
Select Operating Mode
The selected operating mode is displayed inversely:
white battery icon against black background.
Set Parameters at Tester
q Measuring range: in this case always AUTO
Note
After selecting to 2-clamp measurement, switching to the
AUTO range takes place automatically. It is then no longer
possible to change the range!
q Connection type: 2-clamp
q Current clamp sensor transformer ratio:
1:1 (1 V/A), 1:10 (100 mV/A), 1:100 (10 mV/A)
q Distance d (for measuring
E
): irrelevant in this case
Set Parameters at Current Clamp Sensor
q Current clamp sensor measuring range: see table below
Selecting a Measuring Range at the Current Clamp Sensor
Important Instructions for Use of the Current Clamp Sensor
Use only the Z3512A current clamp sensor for this measure-
ment.
•Use the clamp in the permanently connected state. The sensor
may not be moved during measurement.
The current clamp sensor may only be used at an adequate
distance from powerful extraneous fields.
Make sure that the connector cables from the two clamps are
laid separate from each other to the greatest possible extent.
Start Measurement
PROFITEST MPRO, PROFITEST MXTRA
Tester Z3512A Clamp
Transforma-
tion Ratio
Parameter
Switch Measuring
Range
1:1
1 V / A
1 A / x 1 1 A
1:10
100 mV / A
10 A / x 10 10 A
1:100
10 mV / A
100 A / x 100 100 A
R
E
41


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt PROFITEST MXTRA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt PROFITEST MXTRA in the language / languages: English as an attachment in your email.

The manual is 2,28 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Gossen Metrawatt PROFITEST MXTRA

Gossen Metrawatt PROFITEST MXTRA User Manual - Dutch - 92 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info