APPENDIX E/ Common Circuit Connections
Connecting to a Current Transformer (CT)
Safety
precautions
The following safety precautions apply to current transformer (CT) connections in
addition to those safety precautions stated on page E-3.
Never energize a CT with the secondary open.
Never disconnect the secondary of a CT with primary energized.
WARNING
Refer to the manufacturers instructions related to the CT for exact information
for connections for current monitoring. Do not exceed manufacturer’s ratings.
ADVERTENCIA
Consulte las instrucciones del fabricante referentes a TC (transformador de
corriente) para la información exacta de las conexiones a fin de monitorear la
corriente. No exceda las capacidades nominales del fabricante.
AVERTISSEMENT
Se reporter aux instructions du fabricant relatives au transformateur de courant
(Current Transformer - CT) pour obtenir les renseignements exacts sur les
connexions utilisées pour la surveillance du courant. Ne pas dépasser la puissance
recommandée par le fabricant.
WARNUNG
Genaue Informationen zu Verbindungen für die Stromüberwachung entnehmen
Sie bitte den Anleitungen des Herstellers (siehe Stromumwandler). Die
Grenzwerte des Herstellers sollten nicht überschritten werden.
NOTE
Current Transformers are not manufactured by Dranetz-BMI and are discussed here for
informational purposes only.
Description
Current transformers, also known as instrument transformers, reduce high level
currents to low level currents so they can be safely monitored. These devices are
similar to PTs used for voltage measurements in that both reduce values for safe
measurement. The reduction, or step-down ratio, is stated as a scale factor that is used
by the Energy Platform to step-up the measured value to its original value.
Types of CTs
There are single-phase CTs and polyphase CTs dependent on the source transformer
used. Current reduction ratios vary widely and are also dependent on the source
transformer used. Rating plates attached to the CT provide information as to the ratio
and current limitations.
198


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt MAVOWATT 20 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt MAVOWATT 20 in the language / languages: English as an attachment in your email.

The manual is 2,89 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info