B-6
Computed Parameters, continued
True Power
Factor
Calculated using the True Average Power divided by the Apparent Power. See Note
below for sign information.
Displacement
Power Factor
Calculated using cosine of the phase angle between the fundamental frequency
components of voltage with respect to current (0
= 0
V
- 0
I
). See Note below for sign
information.
NOTE
The sign is the exclusive OR of the sign of the Watts and Vars. Note that for Power
Factor, the words “Lead” and “Lag” are definitive. As far as the signs go, it is assumed
that Lag (inductive) is plus and Lead (capacitive) is minus when energy is delivered to
the load.
In the code, this is implemented as:
Signum Watts: cosine 0
Signum Vars: sine 0
Signum PF: (Signum Watts) * (Signum Vars)
where signum denotes the positive or negative sign.
Source: The diagram above matches Figure 9-26 Relationships Between Watts, Vars, and Volt-
Amperes found on page 228 of the Handbook for Electricity Metering, Ninth Edition, ©1992,
Edison Electric Institute, Washington, D.C., USA.
Continued on next page
WATT
TPF
=
VA
PF
=
cos 0
Quad 2
|
Quad 1
PF Lead - | PF Lag +
Watts - | Watts +
Vars + | Vars +
--------------+--------------
Quad 3
|
Quad 4
PF Lag + | PF Lead -
Watts - | Watts +
Vars - | Vars -
167


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt MAVOWATT 20 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt MAVOWATT 20 in the language / languages: English as an attachment in your email.

The manual is 2,89 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info