Nominal Values, continued
Frequency
synchronization
Normal frequency synchronization (sync) of the Energy Platform analog signal
processing circuits is controlled by analyzing the external AC voltage signal input on
channel A. If sync is lost, then internal sync is automatically selected. The frequency
used for internal is entered under Frequency on the Nominal Values screen (see page 5-
14).
Typically, external sync on Ch D is specified if it is known that signal on A is
inappropriate for use as a sync source (i.e. the frequency is unstable or DC). A low
distortion 50, 60 or 400 Hz signal can be input to Ch D and used as a sync signal.
NOTE: Failure to connect an external sync or to select an internal sync during current
monitoring will result in erroneous data being collected and displayed.
Frequency
tracking
Tracking determines how the phase locked loop circuitry responds to sudden changes
in frequency.
Standard mode
: On a normal power quality application [Standard], the system is
designed to “ride through” voltage changes to keep tracking the fundamental frequency
even in the absence of voltage.
Fast mode
: When operating on a local generator [Fast], the frequency will vary more as
loading changes occur. The Fast mode allows the instrument to follow these changes
more closely.
Internal mode
: In cases where no reference signal is available (such as DC monitoring),
the Internal setting is used to set the sample rate.
99


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt MAVOWATT 20 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt MAVOWATT 20 in the language / languages: English as an attachment in your email.

The manual is 2,89 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info