OPERATION
46 SA5
TROUBLE SHOOTING - continued
LED on Remote Control not illuminating, or is
dim when unit is operated
1. Ensure battery is fitted with correct polarity.
2. Ensure battery holder connections are making good
contact with the battery.
3. Battery flat - replace battery.
PIR Movement Detector false alarming
1. Ensure that the detector is not pointing at a source
of heat or a moving object.
2. Ensure that the detector is not mounted above a
radiator or heater.
3. Ensure that the detector is not facing a window or in
direct sunlight.
4. Ensure that the detector is not in a draughty area.
5. Pulse count set too low – reset to two pulse
detection.
PIR Movement Detector not detecting a
person’s movement
1. Ensure the battery clip is securely connected.
2. Ensure ‘House Code’ is correctly set to the same
code as all other system devices.
3. Pulse count set too high - reset to one pulse
detection.
4. Ensure DIP switches 1, 2 and 3 of SW2 are correctly
set, (i.e. 1=ON, 2=ON, and 3=OFF).
5. Ensure that detector is mounted the correct way up,
(i.e. with detection window at the bottom).
6. Ensure that the detector is mounted at the correct
height, (i.e. 2-2.5m).
7. Allow up to three minutes for detector to stabilize
and become fully operational. Leave the area for
this period.
8. Ensure detector is within effective radio range of the
siren and is not mounted close to metal objects
which may interfere with RF transmission.
PIR Movement Detector LED flashes on
detection of movement, (device in normal
operation mode)
1. Ensure that the detector is configured for normal
operation, (i.e. DIP switch 4 of SW2 is OFF).
2. Low battery - replace battery.
Magnetic Contact Detector not working
1. Ensure that magnet is correctly positioned in relation
to detector and that the gap between magnet and
detector is not too large.
2. Ensure batteries are fitted with correct polarity.
3. Ensure battery holder connections are making good
contact with the batteries and PCB.
4. Ensure ‘House Code’ is correctly set to the same
code as all other system devices.
5. Ensure DIP switches 9, 10 and 11 are correctly set,
(i.e. 9=ON, 10=ON, and 11=OFF).
6. If there is no additional Magnetic Contact Detector
connected ensure jumper link is fitted.
7. If an additional Magnetic Contact Detector is
connected:
a. Ensure jumper link is removed.
b. Check that both contacts are closed.
c. Check that additional contact is correctly wired.
Note: If an additional contact is used then the
doors/windows protected by both the main wirefree
detector and the additional wired detector must be
closed when either is opened. If one of the
doors/windows is already open then the opening of
the other door/window will not be detected.
8. Ensure detector is within effective radio range of
Control Panel and is not mounted close to metal
objects which may interfere with RF transmission.
Magnetic Contact Detector false alarming
1. Ensure that magnet is correctly positioned in relation
to detector
2. Ensure that gap between magnet and detector is
less than 10mm.
3. Tamper switch below battery cover not depressed -
check battery cover is fitted correctly and that fixing
lugs are not broken.
Symptom
/
Recommendation Symptom
/
Recommendation
48


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Friedland SA5 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Friedland SA5 in the language / languages: English as an attachment in your email.

The manual is 0,4 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info