• Pipes under a tilt angle:
These are pipes which are vertically ascending at an angle of 30°
or 45° (fig. 12.1 C). Fill in only in combination with at least 2x 30 or
45° bends in the vertical part.
• Restrictor table:
See the restrictor table at the right vertical (TVH) and horizontal
length (THL).
For “x” and if the values are outside the table, then the combination
is not allowed. Only then adjust the TVH or THL.
If a value is indicated, check that the calculated STL value is not
lower than indicated in the table. In this case STL must be adjusted.
The found value indicates the width of the restrictor (“0” means no
restrictor). Standard is a restrictor of 30mm installed (see fig, 2.0 F,
first remove hatch “G”).