INSTALLING INSERTS
When installing inserts, access must be prevented to the internal parts of the appliance and it must not be possible to access live parts during
extraction operations.
Any wiring, for example the power cable or room probe, must be positioned so as not to be damaged during movement of the insert and
must not come into contact with hot parts.
VENTILATION AND AERATION OF THE INSTALLATION PREMISES
Ventilation is deemed sucient when the room is equipped with air inlets according to the table:
Appliance categories Reference standard
Percentage of the
net opening section with respect to
the appliance fumes outlet section
Minimum net opening value of
the ventilation duct
Pellet stoves UNI EN 14785 - 80 cm²
Boilers UNI EN 303-5 50% 100 cm²
* 4pa - reference for Italy according to standard UNI10683. All national, regional, provincial and municipal laws and standards in force in
the country where the appliance is installed must be complied with.
INSTALLATION
GENERAL
The ue gas exhaust and hydraulic connections must be carried out by qualied personnel who must issue installation conformity
documentation compliant with national standards.
The installer must provide the owner or person acting for him, according to the legislation in force, with the declaration of conformity,
supplied with:
1) the use and maintenance manual of the appliance and of the system components (such as for example, the smoke ducts, chimney, etc.);
2) photocopy or photograph of the chimney plaque;
3) system booklet (where applicable).
The installer must ask to be issued with a receipt stating that the documentation has been provided, and must keep it with a copy of the technical
documentation relating to the installation.
For installation in a condominium, prior approval from the condominium's administrator must be requested.
COMPATIBILITY
Installation in premises with re hazards is forbidden. Installation in residential premises (except for sealed operation appliances) is also
forbidden:
in which there are liquid fuel-operated appliances with continuous or intermittent operation, which draw the combustion air in the
room in which they are installed, or
in which there are type B gas appliances intended for room heating, with or without production of domestic hot water and in adjacent
and adjoining premises, or
in which, in any case, the depression measured during installation between the internal and external environment is greater than 4 Pa
*
INSTALLATIONS IN BATHROOMS, BEDROOMS AND STUDIO FLATS
Installation in bathrooms, bedrooms and studio ats is only allowed for sealed or closed hearth appliances with ducted combustion air taken
from the outside.
oor protection
POSITIONING AND SAFETY DISTANCES
The support surfaces and/or points must have a suitable capacity to bear the overall weight
of the appliance, accessories and coverings. If the oor is made of a combustible material,
we recommend using a non-combustible material to protect the front part from any burnt
material which might fall during routine cleaning operations. The generator must be level
to function properly. The adjacent, side and rear walls and the supporting surface must be
made of non-combustible material.
One must also bear in mind all laws and national,
regional, provincial and town council regulations in force
in the country in which the appliance has been installed,
as well as the instructions contained in this manual.
Air inlet
MINIMUM DISTANCES
The appliance may be installed near combustible or heat-sensitive materials as long as
they are placed at appropriate safety distances, specied on the label shown at the
beginning of the manual (page 2). In the event of non-ammable materials there must be
a distance of at least 100mm to the side and to the rear. For products tted with rear spacers,
they can be installed ush with the wall solely with the back against the wall.
6
6


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Extraflame Pellet LCD at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Extraflame Pellet LCD in the language / languages: English as an attachment in your email.

The manual is 5,91 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Extraflame Pellet LCD

Extraflame Pellet LCD User Manual - German - 36 pages

Extraflame Pellet LCD User Manual - Dutch - 36 pages

Extraflame Pellet LCD User Manual - French - 36 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info