VENTILATION AND AERATION OF THE INSTALLATION PREMISES
Ventilation is deemed sucient when the room is equipped with air inlets according to the table:
Air inlet
See gure 2
Appliance categories Reference standard
Percentage of the
net opening section with
respect to the appliance fumes
outlet section
Minimum net opening value of
the ventilation duct
Boilers UNI EN 303-5 50% 100 cm²
In any case ventilation is deemed sucient when the pressure dierence between the external and internal environment is
equal to or less than 4 Pa.
In the presence of type B gas appliances with intermittent operation not intended for heating, they must have their own aeration
and/or ventilation opening. The air inlets must meet the following requirements:
they must be protected with grids, metal mesh, etc., but without reducing the net useful section;
they must be made so as to make the maintenance operations possible;
positioned so that they cannot be obstructed;
The air ow can also be obtained from a room adjacent to that of installation (indirect aeration and ventilation), as long as the
ow takes place freely through permanent openings communicating with the outside.
The adjacent room cannot be used as a garage, warehouse of combustible material or for any other activity with a re hazard,
bathroom, bedroom or common room of the building.
FUMES EXHAUST SYSTEM
GENERAL REQUIREMENTS
Each appliance must be connected to a suitable fumes exhaust system and ensure adequate dispersion of the combustion
products into the atmosphere. The combustion products must discharged above the roof. Direct discharge from the wall or
towards closed spaces is forbidden, even with clear skies.
In particular, it is forbidden to use exible and extendible metal pipes.
The chimney should only receive the exhaust of the smoke duct connected to the appliance; collective ues or conveying
exhausts from hoods above cooking appliances of any kind, or exhausts from other generators into the chimney itself or smoke
duct are not allowed.
The smoke duct and the chimney must be connected with a continuity solution, in order to prevent the chimney from resting
on the appliance.
It is forbidden to have other air supply channels and pipes for plant engineering transit inside the fumes exhaust systems,
especially if over-sized.
The components of the fumes exhaust system must be chosen in relation to the type
of appliance to be installed in compliance with:
in the event of metal chimneys, UNI/ TS 11278, with particular attention to what is stated in the specication;
in the event of non-metallic chimneys: UNI EN 13063-1 and UNI EN 13063-2, UNI EN 1457, .-UNI EN 1806; considering
especially:
temperature class;
pressure class (fumes seal) at least equal to the seal required for the appliance;
moisture resistance (resistance to condensation);
class or level of corrosion and specication of the materials constituting the inner wall in contact with the fumes.
soot re resistance class;
minimum distance from combustible materials
The installer of the fumes exhaust system, once the installation is complete and the relevant checks and inspections have been
made, must x the chimney plaque supplied by the manufacturer with the product in a visible manner, near the replace, and
which must be completed with the following information:
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Extraflame LP20 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Extraflame LP20 in the language / languages: English as an attachment in your email.

The manual is 4.34 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Extraflame LP20

Extraflame LP20 User Manual - German - 40 pages

Extraflame LP20 User Manual - Dutch - 40 pages

Extraflame LP20 User Manual - French - 40 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info