05. FLUE PIPE
CHARACTERISTICS OF THE FLUE PIPE (HYDRO)
HYDRO 20 KW CURVED AND STRAIGHT
FRONT
HYDRO FRONT. 24 KW
CURVED/STRAIGHT
HYDRO KANTINA 20 KW
Chimney flue draught 12
Pa
Chimney flue draught 13
Pa
Chimney flue draught 13
Pa
Fume temperature 154
°C
Fume temperature 179 °C
Fume temperature 145
°C
Maximum flue gas flow rate 10.8
g/s
Maximum flue gas flow rate 14.3
g/s
Maximum flue gas flow rate 10.9
g/s
HYDRO KANTINA 24 KW
HYDRO 13 KW
HYDRO 17.5 KW
Chimney flue draught 13
Pa
Chimney flue draught 12
Pa
Chimney flue draught 10
Pa
Fume temperature 164
°C
Fume temperature 146 °C
Fume temperature 163
°C
Maximum flue gas flow rate 13.2
g/s
Maximum flue gas flow rate 8.4
g/s
Maximum flue gas flow rate 9.6
g/s
FLUE PIPE CHARACTERISTICS (EV STOVE)
EV14
EV20
EV24
Chimney flue draught 10
Pa
Chimney flue draught 13
Pa
Chimney flue draught 11
Pa
Fume temperature 75
°C
Fume temperature 83 °C
Fume temperature 92
°C
Maximum flue gas flow rate 9.5
g/s
Maximum flue gas flow rate 10.7
g/s
Maximum flue gas flow rate 13.1
g/s
EV34
EV50
Chimney flue draught 12
Pa
Chimney flue draught 14
Pa
Fume temperature 95
°C
Fume temperature 137 °C
Maximum flue gas flow rate 19.0
g/s
Maximum flue gas flow rate 25.7
g/s
Use a vent pipe and an anti-corrosion fume connection to the vent pipe. The temperature of the pellet stove fumes is very low. It could create condensation and
corrode the fume exhaust.
The flue pipe is one of the key features for guaranteeing correct functioning of the stove. Thanks to the quality of the materials, the strength, the durability, the
easy cleaning and maintenance, the best flue pipes are made of steel, either stainless steel or aluminised.
The stove is fitted with a Φ 80mm rear round fume outlet and a joint connection to be connected to the vent pipe.
In order to facilitate connection to the rigid steel flue, it is advisable to use telescopic fittings which, in addition to
facilitating the procedure, also compensate for the thermal expansion of both the firebox and the flue itself.
Seal the vent pipe joint connection with high temperature silicone sealant (1,000°C). In the event that the mouth of
the existing flue pipe is not perfectly perpendicular to the fume outlet of the fire box, their connection must be made
using a dedicated inclined fitting. The angle with respect to the vertical must never exceed 45° (see figure to the
side) and there must be no bottlenecks.
In case of passage through floors, an insulating sleeve of 10 cm thickness must be interposed.
The flue pipe must be insulated along its entire length. The insulation will make it possible to maintain a high fume
temperature to optimise the draught, avoid condensation and to reduce deposits of unburnt particles on the walls
of the flue. Use proper insulating materials (glass wool, ceramic fibre, Class A1 non-combustible materials).
The flue must be weatherproof and must not make more than two changes of direction.
Flexible and length-adjustable metal pipes may not be used.
EXISTING VENT PIPE EXTERNAL VENT PIPE
Types of vent pipe
Steel flue pipe with double chamber insulated with
material resistant to 400°C. Optimum efficiency.
Refractory flue pipe with insulated double chamber and
external coating in lightweight concrete. Optimal
efficiency.
Avoid flue pipes with internal rectangular section whose
ratio between the larger and smaller side is greater than 1.5.
Poor efficiency
Traditional clay flue pipe with cavities. Optimal efficiency.
MAX A+1/2A
A
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Eva Calor Hydro17.5 KW at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Eva Calor Hydro17.5 KW in the language / languages: English as an attachment in your email.

The manual is 4.77 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Eva Calor Hydro17.5 KW

Eva Calor Hydro17.5 KW User Manual - German - 43 pages

Eva Calor Hydro17.5 KW User Manual - Dutch - 43 pages

Eva Calor Hydro17.5 KW User Manual - French - 43 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info