668833
8
Zoom out
Zoom in
Previous page
1/55
Next page
Fig. 5
Table 2
Roof pitch ? [°]
Horizontal width of
the zone of reflux
from the axis of the
ridge A[m]
Minimum height of
the outlet from the
roof Hmin
=Z+0.50m
Height of the reflux
zone Z [m]
15 1.85 1.00 0.50
30 1.50 1.30 0.80
45 1.30 2.00 1.50
60 1.20 2.60 2.10
1.3 External air intake vent
-The stove must have the air necessary to ensure smooth combustion operation and good
environmental well-being.
-Make sure that the room where the stove is installed offers sufficient ventilation and install an air
supply duct from the outside with the recommended minimum section of 100 cm².
-The air intake vent must communicate directly with the installation room of the stove, positioned so
as to prevent it from being blocked and protected with a permanent non-lockable grid or other
suitable protection provided that it does not reduce the minimum section.
-Air flow can also be obtained from a room adjacent to the installation room, provided that this flow
can be carried out freely through permanent, non-closable openings communicating with the outside.
-With respect to the installation room, the adjacent room should not be put under vacuum with
respect to the external environment as a result of a reverse draft caused by the presence in this
space of another utility device or suction device. The room adjacent to the permanent openings must
meet the requirements set out in the paragraphs above. The adjacent room cannot be used as a
garage, for storage of combustible material or for activities involving a risk of fire.
1.4 Connection to the chimney flue
(see paragraph 4.5)
1.5 Preventing house fires
Installation and use of the stove must be in accordance with the manufacturer's instructions and with
local habitability regulations.
CAUTION: when a fume exhaust pipe passes through a wall or ceiling, particular installation methods
must be applied (protection, thermal insulation, distances from heat sensitive materials, etc.).
- The fireplace connecting tube must never pass through a combustible surface.
- Do not connect this unit to a chimney flue already being used by another device.
-It is also advisable to maintain all combustible elements or flammable material such as beams,
wooden furniture, curtains, flammable liquids, etc. outside the radiation area of the furnace and at
a distance of at least 1 m from the heating block. .
-In the event that the surrounding space has coverings in combustible or heat-sensitive material, a
protective membrane made of non-combustible insulating material must be interposed. If the flooring
is made of combustible material, a non-combustible protective material that protrudes laterally and
frontally from 15cm to 30 cm must be provided at the mouth of the furnace.
- For further information, refer to local requirements.
2 SPECIFICATIONS AND TECHNICAL DATA
2.1 Specifications
Stoves and pellet stoves are devices built to work with good quality wood pellets only (see par. 3
fuel). Hydro models must be connected to the plumbing system.
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Eva Calor Hydro Kantina 34 kW auto at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Eva Calor Hydro Kantina 34 kW auto in the language / languages: English as an attachment in your email.

The manual is 5,06 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info