Menu: Heating circuits
Optimum start / stop control
Optimum start control max
The change from one temperature level
to the other is optimized in a way that
the comfort setpoint is reached at the
relevant switching time.
Optimum stop control max
The change from one temperature
level to the other is optimized in a
way that the comfort setpoint minus
1
/
4
°C is reached at the relevant
switching time.
Optimum start / stop control is pos-
sible with or without room sensor.
Raising the reduced setpoint
The function is used primarily in
connection with heating systems with
only little spare capacity (e.g. low-
energy houses).
In such cases, the heating up time
would be too long at low outside
temperatures. When the reduced
setpoint is raised, the rooms are
prevented from cooling down to too low
levels, thus shortening the heating up
time when changing to the comfort
setpoint.
Line no.
Operating line
Factory setting
HC1
HC2
790
1090
Optimum start control max
0
791
1091
Optimum stop control max
0
Line no.
Operating line
Factory setting
HC1
HC2
800
1100
Reduced setp increase start
- - -
801
1101
Reduced setp increase end
- 15°C
TRw Room temperature setpoint
TRx Actual value room temperature
Xoff Switch-off time shifted forward in time
Xon Switch-on time shifted forward in time
ZSP Time switch program
TAgem Composite outside temperature
TRK Comfort cooling setpoint
TRR Reduced room temperature setpoint
TRwA1 Reduced setpoint increase start
TRwA2 Reduced setpoint increase end
27
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Elco Thision S at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Elco Thision S in the language / languages: English as an attachment in your email.

The manual is 2,06 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Elco Thision S

Elco Thision S User Manual - German - 20 pages

Elco Thision S User Manual - Dutch - 21 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info