Commissioning
Combustion analysis
16
Combustion settings
for natural gas G20 / G25
R601-R607
CO
2, max
% 10.2 ± 0.2
CO
max
ppm < 30
Combustion settings
for LPG G31
Convert boiler before operation
(see coversion kit instruction)
R601-R607
CO
2, max
% 11.9 ± 0.2
CO
max
ppm < 30
Combustion check at full load
Start the boiler in controller stop mode
and go to full load operation (100%).
Now the boiler operates at 50% load.
Allow the boiler to stabilise the
combustion for 3 minutes. Then
increase the boiler load step by step up
to 100%. Check the gas pressure on
the inlet of the gas valve while increa-
sing the boiler load: the gas pressure
should never go below the minimum
required value see technical data.
Set the minimum gas pressure switch
(1) at 75% of the required gas pressu-
re.
Check the combustion settings via the
test point in the chimney connection(3).
If necessary, correct the settings with
the flat adjustment screw on the outlet
of the gas valve (2).
Combustion settings
for natural gas G20 / G25
R601-R607
CO
2, min
% 9.4 ± 0.2
CO
min
ppm < 30
Combustion settings
for LPG
G31
Convert boiler before operation
(see coversion kit instruction)
R601-R607
CO
2, min
% 10.0 ± 0.2
CO
min
ppm < 30
Combustion check at minimum load
Switch the boiler to minimum load (0%).
Check the combustion settings the
same way as described for full load. If
necessary, correct the settings with the
allen key adjustment screw on either
side of the gas valve (4).
Combustion check at 50% load
An additional reference check of com-
bustion values at 50% load is recom-
mended in order to check if the gas
valve is set in such way, that the modu-
lating behaviour is normal. The CO
2
value should be in between the settings
of full load and minumum load. CO
value should be equal to full load and
minimum load values.
Make sure that the boiler is set to auto-
matic operation and controller stop mo-
de is disabled after the combustion test
is finished.
2
4
R601
R602 - R607
1
2
4
3
18


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Elco R600 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Elco R600 in the language / languages: Dutch as an attachment in your email.

The manual is 4,15 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info