Hydraulic connection
Water heater
The R600 water heater must be installed in such a way, that a minimum water flow rate of
30% of the nominal flow rate can be assured at all times when the burner is switched on. The
R600 water heater can increase the water temperature by maximum 17K at once. This
means that the water has to cycle through the boiler several times when f.e. cold water of
10ºC has to be heated up to 60ºC (3 times).
This is normally done by installing the R600 water heater in combination with a buffer tank.
The flow rate from the tank to the water heater and back can then be secured by the
(primary) water heater pump.
The table below shows the nominal water flow data at a T of 17K, plus the pump data of the
(optional) pump kit for each type of water heater.
Water flow data water heater
T Nominal
flow rate
Boiler
resistance
Pump type Voltage Curve
setting
Pump
head
Residual
pump head
[K] [m3/h] [kPa] [-] [V] [-] [kPa] [kPa]
R601
17
7.2 14 UPS 32-80B 230
3
-
34
-
20
-
R602 9.5 25 UPS 32-120FB 230
3
2
61
30
36
5
R603 12.0 39 UPS 40-120FB 230
3
2
64
48
25
9
R604 14.4 21 UPS 40-120FB 230
3
2
50
30
29
9
R605 19.2 37 UPS 50-120FB 400
3
2
64
47
27
10
R606 24.0 58 UPS 65-120FB 400
3
-
76
-
18
-
R607 27.2 76 UPS 65-180FB 400
3
-
104
-
28
-
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Elco R600 IP-ZW at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Elco R600 IP-ZW in the language / languages: English, German, Dutch, French, Italian as an attachment in your email.

The manual is 0,68 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info