Installation
Electrical connections
General Information
Electrical installation and connection
must be carried out by an authorised
installer in accordance with applicable
National Standards, Local Standards
and Regulations.
Mains connection and Customer
wiring
The appliance is designed for
permanent connection using cables
NYM 3x1.5 mm2 or H05W-F 3 x 1
mm2. The connection cable should not
be larger than 8 mm in diameter.
Connect the mains wiring to the
respective terminals, on the Boiler
Terminal strip, in the 240V section at
the rear of the control panel. (See
picture below)
A suitable mains isolator switch must
be fitted in the power supply, to the
boiler, and sited in the boiler room.
This can be used to switch off power
to the boiler for maintenance purposes
or in the event of a problem.
Mains voltage: 230 V, 50 Hz
Mains cable Connection
All external connection cables should
be stripped to a max. 30 mm. All
external Cables entering the Boiler
must be firmly clamped in the Cable
grip after connection
The length of the cables must be
designed accordingly. Additional
cables (e.g. for system integrations),
which are attached to the terminal strip
in the boiler, must be secured along
with mains lead via the Cable grip.
When connecting the boiler, ensure
the earth cable (yellow/green), which
is longer than the supply wires (see
illustration) is connected.
Multiple plug sockets, extension cable
and adapter are not appropriate. For
earthing of the appliance under no
circumstances use the piping of the
water supply installation, heating or
gas installation.
Please note the appliance is not
protected against damage from
lightning strikes.
If the mains fuses are to be changed,
use 2A Quick Blow fuses.
Note before any connections are
made below the boiler must be
switched Off.
Remote Operation (Volt Free)
A volt free enable to the Boiler for a
Thermostat, Time switch etc, is
possible via X10-02 (2)
Remote Operation (QAA73)
Connection (1) for a QAA73 must
be via a cable with at least. 2 x 0,5
mm2.
The "Bus" cable of the QAA73
(20-30 V) must be installed and
run separately from the 230 V/50
Hz cables. The QAA73 connects
to the X10-01 connector using
screened cable.
Note: If the QAA 73 remote
control is being used, the
thermostat bridge must be
disconnected from the X10-02 (2)
connection.
Note: Only one type of Boiler
enable can be used via either
X10-01 or X10-02
Ambient / External Sensor
(QAC34)
Connect the Outside Air
Temperature sensor (3), if
required, using a Screened Cable
with at least 2 x 0,5 mm
2
, with a
maximum length of 50m.
The sensor should be positioned
on a North Facing Wall at a height
of 2 2.5 m above the floor. Under
no circumstances must it be
directly exposed to sunlight.
Connect the ambient/external
sensor to the X10-06 (3)
connector (using screened cable).
Safety Thermostat for
Underfloor Heating
Remove the bridge loop from the
terminals on the right hand side of
the Terminal Block, on the 240v
connection side, and connect the
safety thermostat for the
underfloor heating.
The Connections on the boiler
wiring side will be pre-wired back
to X3-01 on the LMU unit.
Earth Block
240v Mains Power Connection
240V Connection.
1
st
TwoTerminals
Connection for
Underfloor limit
thermostat
Cable Grip
15


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Elco MHS - EURON 24 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Elco MHS - EURON 24 in the language / languages: English as an attachment in your email.

The manual is 2,98 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info