8.9. The chimney pot
Must be windproof.
Must have an inner cross-section equivalent to that of the chimney flue and an outlet smoke passage cross-
section equal to at least twice the inner cross-section of the chimney flue.
In the case of paired chimney flues (which should be at least 2 m apart), the chimney pot that receives the solid
fuel product discharge or that of the highest floor must be at least 200 cm above the other.
Must go beyond the reflux area (in Italy, refer to Standard UNI 10683)
Must allow for maintenance operations to be performed on the chimney
8.10. Indirect air intake
Prepare, at floor level, an air intake with a useful surface area (net of any meshes or other protections) of at least 80
cm2 (diameter 10 cm).
In order to avoid draughts, it is advisable to place the air intake behind the stove or behind a radiator.
It is advisable not to have it in front of the product to avoid draughts.
The inflowing air can come from an adjacent room provided that:
The flow does not encounter any obstacles as it travels though permanent openings communicating with the
outside
The room adjacent to the installation room is never depressurised with respect to outside.
The adjacent room is not used as a garage or for activities causing a risk of fire, nor is it a bathroom or a bedroom.
The adjacent room is not a common room of the building
In Italy, Standard UNI 10683 indicates that ventilation is sufficient even if the pressure difference between the external
and the internal environment is maintained at 4 Pa or less
The installer who issues the declaration of conformity is responsible for this.
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for EK63-EdilKamin Decor Evo at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of EK63-EdilKamin Decor Evo in the language / languages: English as an attachment in your email.

The manual is 2.03 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of EK63-EdilKamin Decor Evo

EK63-EdilKamin Decor Evo Usermanual and installation guide - German - 44 pages

EK63-EdilKamin Decor Evo Usermanual and installation guide - Dutch - 44 pages

EK63-EdilKamin Decor Evo Usermanual and installation guide - French - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info