ENGLISH
FLUE SYSTEM
FLUE SYSTEM
(
(
Fumes duct, flue and chimney pot
Fumes duct, flue and chimney pot
)
)
This chapter has been drawn up pursuant to European
regulations EN 13384, EN 1443, EN 1856 and EN
1457. The installer must observe both these and any
other local regulations. This manual does not in any
way substitute such regulations.
The product must be connected to a flue system which
ensures that the fumes produced by combustion are
expelled in complete safety.
Before positioning the appliance, the installer must
check that the flue is suitable.
FUMES DUCT, FLUE
FUMES DUCT, FLUE
The fumes duct
(which connects the combustion
(which connects the combustion
chamber smoke outlet with the flue)
chamber smoke outlet with the flue) and the flue itself
must, among other regulatory requirements:
receive the fumes from a single product (the outlets
of multiple appliances may not be conveyed into
a single flue)
be routed vertically for the most part
have no downwards sloping sections
preferably have a circular internal cross section, or
with a ratio of the sides of less than 1.5
terminate at roof level with a proper chimney pot:
the flue may not discharge directly on the wall
or into an enclosed space, even if the space in
question is open to the sky
be made of material with rated fire reaction class
A1 as per UNI EN 13501 or analogous national
regulations
be certified, with a chimney plate if metal
be of uniform cross section or vary in cross section
only immediately after the outlet, not at some mid-
point of its length.
THE FUMES DUCT
THE FUMES DUCT
Further to the general prescriptions for the fumes duct
and flue, the fumes duct:
may not be made of flexible metal material
must be insulated, if routed through unheated
areas or outdoors
must not be routed through rooms where the
installation of combustion heat generators is
prohibited or there is risk of fire, or that cannot be
inspected
must enable the recovery of soot and be open for
inspection
must have a maximum of 3 bends with a maximum
angle of 90°
if there is a horizontal section, it can have a
maximum length of no more than 3 metres,
depending on the draw. Note, in any case, that
long sections encourage the accumulation of dirt
and are harder to keep clean.
THE FLUE
THE FLUE:
Further to the general prescriptions for the smoke duct
and flue, the flue
:
:
must only be used for discharging fumes
must be correctly sized to satisfy the requirements
for fume discharging (EN 13384-1)
should preferably be insulated, in steel with a
circular internal section. If rectangular, the corners
must have a radius of not less than 20 mm, with a
ratio of the internal dimensions of <1.5
must normally be at least 1.5 metres in vertical
length
must have a constant cross section
must be waterproof and thermally insulated to
ensure a good draw
preferably provide a collection chamber for
unburnt residues and condensates
if pre-existing, must be clean, to prevent fire
hazards
in general, we recommend fitting a tube inside the
existing masonry chimney if its diameter is greater
than 150 mm.
INSTALLATION
INSTALLER
INSTRUCTIONS FOR THE SMOKE DISCHARGE
INSTRUCTIONS FOR THE SMOKE DISCHARGE
WITH OR WITHOUT CONCENTRIC PIPE
WITH OR WITHOUT CONCENTRIC PIPE
10


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Edilkamin Vyda 2 Air Tight at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Edilkamin Vyda 2 Air Tight in the language / languages: English as an attachment in your email.

The manual is 1.8 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Edilkamin Vyda 2 Air Tight

Edilkamin Vyda 2 Air Tight Usermanual and installation guide - German - 40 pages

Edilkamin Vyda 2 Air Tight Usermanual and installation guide - Dutch - 40 pages

Edilkamin Vyda 2 Air Tight Usermanual and installation guide - French, Italian - 76 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info