THE SMOKE CHANNEL
•ifinmetalmusthaveaCEmarking(EN1856-2)or
similar national law;
•cannotbeinflexiblemetalmaterial
•
to check the flow, a shutter is advised for draft over
25 Pa
THE CHIMNEY FLUE:
• must have a draft capable of creating negative
pressure ideally around 12 Pa. Lower drafts can
cause leaking smoke if the door is open; higher
values tend to generate fast combustion by redu-
cing the yield
• must be correctly sized to meet smoke evacuation
(EN 13384-1)
• must preferably be insulated, in steel with a circular
inner section. If rectangular, the inner edges must
have a radius under 20 mm and a ratio between
between the inner dimensions <1.5
• normally have a minimum height of 3-4 metres
• maintain a constant section
• be waterproof and thermally insulated to guaran-
tee draft.
• preferably create a collection chamber for unbur-
ned fuel and any condensate
• be at least category T400, with an adequate resi-
stance to soot fireIf pre-existing, it must be clea-
ned to avoid risk of fire.
THE CHIMNEY STACK
• must be wind-proof
• have an internal section equivalent to that of the
chimney flue and passage section outlet equal to
at least double the inner passage of the chimney
flue
• for paired chimney flues (which should be at least
2 m apart) the chimney stack of the chimney flue
receiving the product discharge with solid fuel or
that of the highest floor must be at least 50 cm
taller
• must go beyond the reflux zone
• must enable chimney maintenance
INSTALLATION
CHIMNEY SYSTEM
(Smoke channel, chimney ue and chim-
ney stack)
This chapter is drafted according to the European
Standards EN 13384, EN 1443, EN 1856, EN 1457.
The installation technicians must take into considera-
tion these and any other local standards. The manual
should in no way be considered a replacement for the
laws in force.
The stove must be connected to a suitable smoke di-
scharge that guarantees completely safe evacuation
of the smoke produced by combustion.
Before positioning the stove, you need to check the
chimney flue is suitable.
The fumes outlet is at the top.
SMOKE CHANNEL, CHIMNEY FLUE
The smoke channel (pipe that connects the smoke
outlet of the fireplace with the chimney flue inlet) and
the chimney flue must, along with other legal provi-
sions:
• receive the discharge for a single product (multiple
product discharges are not permitted together)
• have a mainly vertical development
• no section should have a reserve slope
• have an inner section preferably circular and
however with a ratio between sides lower than 1.5
• complete the roof with the appropriate chimney
stack: direct discharge is forbidden on walls or
towards closed spaces, even if outdoors
• be created with materials with a fire reaction class
A1 pursuant to UNI EN 13501 or similar national
standard
• be appropriately certified, with an appropriate
fireplace plate, if metal
• keep the initial section.
10


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Edilkamin Cubira at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Edilkamin Cubira in the language / languages: English as an attachment in your email.

The manual is 3.14 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Edilkamin Cubira

Edilkamin Cubira Usermanual and installation guide - German - 20 pages

Edilkamin Cubira Usermanual and installation guide - Dutch - 20 pages

Edilkamin Cubira Usermanual and installation guide - French, Italian - 40 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info