38
EXAMPLES OF AIRTIGHT INSTALLATION.
Reduction of the air intake pipe section and gas output section is strictly forbidden.
Ignore section 4.22 in case of airtight installation.
It must be installed in a room with positive atmospheric pressure (minimum 5 pascals). Never make it
work in depression (airtight rooms or without the due air renovations).
Please note below two kinds of airtight installations:
4.29. “DIFLUX” piping.
The gas outlet and the combustion air inlet are connected to the concentric "Diflux" tube. After the air intake
you will find immediately on the outside, the rest of pipe sections should be in double wall pipe.
Drawing 11
For these installations it is highly advised to modify the depression offset, according to the number of pipe
sections installed. See the following chart:
Gas
outlet pipe sections
Offset adjustment
“Depression” (PA)*
≤ 3m
+ 5.0
4m
+ 8.0
> 4m
+8.0 ≥ Adjustment ≤ +14.0
Drawing 12
* Check modification over the offset with the stove working on level 1 and 9 during 1 hour, controllong the right
combustión of the stove ( no smoke, no depressure excess, etc).
4.30. Air inlet connected directly to the outside.
Air intake pipe.
Combustion air intake.
Gas output >2m. Double wall pipe in the
outside.
Windbreak.
Connection of stove to combustion gas outlet.
Stainless steel hose clamp.
39


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ecoforest Hidrocopper 24 - Slim at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ecoforest Hidrocopper 24 - Slim in the language / languages: English, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 15.07 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Ecoforest Hidrocopper 24 - Slim

Ecoforest Hidrocopper 24 - Slim User Manual - English, German, Dutch, French, Italian, Portuguese, Spanish - 228 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info