36
4.25. The air input pipe should not be drained with the risk of affecting the correct operation of the stove. For this
reason, and in order to facilitate fresh air input, it is necessary to set up a ventilation grid AT NOT LESS than
50cm both horizontally and vertically from gas output, see point 4.19.
Direct air currents shall also be avoided as they might prevent a correct operation of the stove and as a
consequence, heat performance.
Ventilation of the room must meet the minimum flow required according to specific regulations and the
maximum intake air flow of the machine.
Extraction fans can cause problems when operating in the same room or in the same space as the appliance.
4.26. In any case the design of the chimney termination will impede the free diffusion in the atmosphere of
combustion products. A metallic mesh with a gap of 3x3 cm can be placed to avoid the entry of birds or
unwanted objects.
4.27. If a testing module is installed to collect combustion gas readings and samples, it must be equipped with
hermetic and self-locking sealing.
EXAMPLES OF FLUE INSTALLATIONS.
Although we cannot keep track of or describe every single installation, option, or the local installation
regulations corresponding to your area, Ecoforest guarantees that the installations suggested below will enable
your stove to function properly, and to conform to minimum personal and material safety measures.
If you are installing your stove in a building, in addition to respect local regulations on gas flues, you should
consult with the residents’ association to avoid future problems.
Please read the entire manual carefully, especially the chapter on installation to ensure your stove
operates properly and at full power.
If the total pipe length exceeds 8m, it is recommended to increase one measure, being able to make the
whole assembly in the same diameter from the connection of the stove or increase section from 4 m.
4.28. The installation shown below is the most common. Please bear in mind that if the gas flue pipe located on
the outside of the dwelling is in an area where people pass by, insulated tube must be used.
Drawing 13
4.29. If for aesthetic, safety or municipal regulations we cannot install the stove as described above, we can always
install the pipe on the inside of the dwelling, paying special attention to the areas where the pipe touches
structures, and the minimum vertical and maximum horizontal lengths.

Windbreak
.

Stainless
steel hose clamp.

T of
90
° with outlet
.

Insulator
.

Wooden ground
.

Non flammable floor protection
.

Distance equal to or less than 2 metres.
37


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ecoforest Granada at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ecoforest Granada in the language / languages: English, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 9,82 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Ecoforest Granada

Ecoforest Granada User Manual - English, German - 228 pages

Ecoforest Granada Installation Guide - Dutch - 208 pages

Ecoforest Granada User Manual - Dutch, French, Italian, Portuguese, Spanish - 228 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info