PLEASE NOTE: 45H IS FOR OUTDOOR PERMANENT INSTALLATIONS ONLY AND 45HI IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL
AND ALL ECCOTEMP CONTECT IS SUBJECT TO CHANGE WITHOUT NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
Phone: 866-356-1992 | Email: Support@eccotemp.com | Address: 315 - A Industrial RD Summerville, SC 29483
English
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
Relief Valve
• The pressure rating of the relief valve must not exceed
150 psi, the maximum working pressure of the water
heater as marked on the rating plate.
• The BTUH rating of the relief valve must equal or exceed
the BTUH input of the water heater as marked on its
rating plate.
• No valve of any type should be installed between the
relief valve and the water heater.
• Discharge from the relief valve should be piped to a
suitable drain to eliminate potential water damage. Piping
used should be of a type approved for the distribution of
hot water.
• Hot and cold water lines should be insulated up to the
water heater.
• The discharge line must be NO SMALLER than the outlet
of the valve and must pitch downward to allow complete
drainage (by gravity) of the relief valve and discharge line.
• The end of the discharge line should not be threaded or
concealed and should be protected from freezing. No
valve of any type, restriction or reducer coupling should
be installed in discharge line.
NOTICE: Local codes govern the installation of relief valves. If local codes require that a temperature
and pressure relief valve should be installed the manufacturer recommends a type 40XL Watts T&P
relief valve or an equivalent model be used.
NOTICE: Manual operation of relief valves should be performed at least once a year. Turn o the
electrical power and gas shuto valve. Lift and release lever on the relief valve and check the manual
operation of the relief valve. You should take precaution to avoid contact with the hot water coming
out of the relief valve and to prevent water damage.
NOTICE: If the relief valve on the system discharges periodically, this may be due to thermal expansion
in a closed water supply system. Contact the water supplier or local plumbing inspector on how to
correct theis situation. Do not plug the relief valve.
A new pressure relief valve, complying with the Standard for relief Valves and Automatic Gas Shut-O
Devices for Hot Water Supply Systems, ANSI Z21.22, must be installed at the hot water outlet connection of
the water heater at the time of installation. Local codes shall govern the installation of relief valves.
For safe operation of the water heater, be sure that:
NOTICE: The above illustrates
a pressure only relief valve.
If local codes require a
combination temperature
and pressure relief valve be
installed, an extension piece
may be needed.
Pressure Testing the Gas Supply System
WARNING: Install a gas pressure regulator, in the gas supply line, which does not exceed the
maximum supply pressure.
DO NOT use an industrial type gas regulator.
Failure to isolate heater during pressure test can damage internal components voiding warranty. The water heater
and its individual shuto valve must be disconnected from the gas supply piping system during any pressure
testing of that system at testy pressures in excess of 1/2 psi. The water heater must be isolated from the gas
piping system by closing the manual gas shut-o valve during any pressure testing of the gas supply piping at test
pressures equal to or less than 1/2 psi (14’w.c.).
45-H
15


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Eccotemp 45H-LP at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Eccotemp 45H-LP in the language / languages: English as an attachment in your email.

The manual is 17.17 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info