INSTALLATION MANUAL
5.8.3 Placing the concentric system
!Caution
Maintain a distance of at least 50 mm between the outside of the concentric system and the walls and/or the
ceiling (see section 5.4). If the system is built in (for instance) a cove, it should be made with non combustible,
heat-resistant material all around it.
Use heat-resistant insulation material when passing through combustible material.
Create a terminal for the concentric system with the following diameters:
- The pipe diameter +25 mm for a passage through non combustible material (see Appendix 3, fig. 40).
- The pipe diameter +200 mm for a passage through combustible material. Insulate the surrounding free
space with at least 60 mm mineral wool (see Appendix 3, fig. 41).
The rosette of the wall terminal is too small to seal the opening in case of passage through combustible
material. That is why a heat-resistant intermediate plate of sufficient size should first be mounted to the wall.
Then, the rosette is mounted on the intermediate sheet.
The roof terminal can end in a sloping and a flat roof.
The roof terminal can be supplied with an adhesive plate for a flat roof or with a universally adjustable tile for a
sloping roof.
!Caution
Some heat-resistant insulation materials contain volatile components that will spread an unpleasant smell for a
prolonged time; these are not suitable.
Place the concentric system as follows:
Ø
Build the system up from (the flue spigot of) the appliance.
Ø
Connect the concentric pipe pieces and, if necessary, the bend(s).
Ø
On each connection, apply a clip binding with silicon sealing ring.
Ø
Use a self-tapping screw to fix the clip binding to the pipe on locations that cannot be reached after installation.
Ø
Attach the concentric system with sufficient fastening brackets, so that the weight is not resting on the appliance.
Observe the following;
Place the first fastening bracket 0.5 metre from the appliance, at the most.
Place a fastening bracket maximum 0.1 metre from each bend, if the bends are more than 0.25 metre away
from each other. If two bends are closer to one another than 0.25 metre, 1 fastening bracket between these
bends will be sufficient.
At least every 1 metre, place a fastening bracket at slanted and horizontal sections.
At least every 2 metres, place a fastening bracket at vertical sections.
Ø
Fasten a roof terminal with anchor cables, if it protrudes more than 1,5 metres above the terminal.
Ø
Determine the remaining length for the wall or roof terminal and cut it to size, make sure the correct insertion
length is maintained.
Ø
Place the wall terminal with the (groove/folded) seam at the top.
Ø
Attach the wall terminal from the outside by means of four screws.
!Caution
When using the wall terminal, place the terminal with a downward slope of 1 cm / metre towards the outside, in
order to prevent rain water from raining in.
5.9 Connection to an existing chimney (C91)
The appliance can be connected to an existing chimney. A 100 mm diameter flexible SS pipe is placed in the
chimney for discharging flue gases. The surrounding space is used as combustion air supply.
In case of an appliance connection of ø200/130, 0.8 metres of concentric system must first be connected vertically.
Reduce the concentric system after the first 0.8 metres to a diameter of 150/100. The concentric system of 150/100
can be vertically connected to an existing chimney.
The following requirements apply when connecting to an existing chimney:
Only allowed when used in combination with the special DRU chimney set. The installation regulation is parat
of the delivery.
The internal size should be at least 150 x 150 mm.
The vertical length has a maximum of 12 meters.
The total horizontal pipe length may have a maximum length that can be found in appendix 2, table 4.
The existing chimney should be clean.
The existing chimney should be tight.
For setting the appliance, the same conditions/instructions apply as for the concentric system described above.
11
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for DRU Cosmo Tunnel at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of DRU Cosmo Tunnel in the language / languages: English as an attachment in your email.

The manual is 8.69 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of DRU Cosmo Tunnel

DRU Cosmo Tunnel User Manual - English - 28 pages

DRU Cosmo Tunnel User Manual - German - 28 pages

DRU Cosmo Tunnel Installation Guide - German - 40 pages

DRU Cosmo Tunnel User Manual - Dutch - 28 pages

DRU Cosmo Tunnel Installation Guide - Dutch - 40 pages

DRU Cosmo Tunnel Installation Guide - French - 40 pages

DRU Cosmo Tunnel User Manual - French - 28 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info