• Determine the length of the pipes required and ensure
that the adhesive flashing or the universal tile fit properly.
• Saw the outside pipe off at the length required.
• Connect the roof duct to the concentric pipes.
NB: Alternatively, you can fit the concentric pipes before
installing the heater. In that case the connection to the
outlet of the appliance should be made using a length of
pipe that can be shortened later.
Fitting the fire to an existing chimney
The fire can be fitted into an existing chimney providing
that the chimney / flue dimensions are 150 mm or more.
A special flue kit is required, which can be obtained from
Drugasar or a Drugasar agent. Do not use any other type
of flue system for this.
BS 5871 – 1 : 2001
Any chimney previously used for an appliance burning a
fuel other than gas shall be swept thoroughly before
installing any gas appliance.
Appliances shall be connected only to the types and sizes
of flue system as specified.
For any other information about this flue system please
contact Drugasar or Drugasar approved agent.
Baffle/Sliding air valve
To ensure that the appliance
works satisfactorily,
it will need to be adjusted
according to the
customer-specific pipe system.
Adjusting the baffle.
The baffle is supplied separately and should be fitted into
the heater as indicated in fig. 5. Use the adjustment jig
provided (fig. 4) to adjust the baffle to the right size. Once
it has been adjusted, fix the damper in place with the
socket-head screw.
Removing the sliding air valve, see fig. 6: remove the back
burner by unscrewing the two self-tapping screws (2).
Undo the three wing-nuts (3) and remover the two-part
sliding air valve (1). Replace the burner.
Connecting the Gas Supply
An approved connecting tap with coupling should be used
in the supply hose (In Belgium this must be B.G.V. approved).
Furthermore:
• Expel all air from the supply pipes/hoses before coupling
to the appliance.
• Do not turn the coupling tap when connecting it to the
gas supply.
Avoid any pressure on the control tap and pipes.
• Check that all connections are gastight.
English
Cello
INSTRUCTIONS FOR INSTALLATION
15
45
50
55
fig. 4
G25/G20
Luchtschuif
(fig. 6)
Distance
baffle
(fig. 5)
1 - 2 metres
vertical + roof duct (*)
YES
55 mm
2 - 6 metres
vertical + roof duct (*)
YES
50 mm
6 – 12 metres
vertical + roof duct (*))
YES
45 mm
0,5 – 1 m vertical
+ 90˚ bend
+ wall duct
NO OPEN
0,5 m vertical + 90˚ bend
+ max 2 m horizontal
+ wall duct (**)
NO OPEN
1 m vertical + 90˚ bend
+ max 4 m horizontal
+ wall duct (**)
NO OPEN
(*) NB: The maximum length of vertical pipe is 12 metres.
(**) NB: the maximum length of horizontal pipe must not be exceeded.
Fig. 3 illustrates how to calculate the total lengths of pipe.
Sliding
air valve
(fig. 6)
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for DRU CELLO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of DRU CELLO in the language / languages: English, German, Dutch, French as an attachment in your email.

The manual is 0,82 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info