571320
35
Zoom out
Zoom in
Previous page
1/182
Next page
The flue or chimney must be made of fire resistant
material, preferably ceramics or stainless steel.
The flue or chimney must be airtight and well
cleaned and guarantee sufficient draught.
A draught/vaccuum of 15-20Pa during normal
operation is ideal.
Starting from the flue spigot, the flue must run as
vertically as possible. Changes in direction and
horizontal pieces disrupt the outward flow of
combustion gases and may cause the deposit of
soot.
The interior measurements should not be too big, to
prevent the combustion gases from cooling down
too much, thereby reducing the draught.
The flue or chimney must ideally have the same
diameter as the connection collar.
For the nominal diameter: see the appendix
"Technical data". If the smoke channel is well
insulated, the diameter may be slightly bigger
(up to 2x the section of the connection collar).
The section (area ) of the smoke channel must be
constant. Wider segments and (in particular)
narrower segments disrupt the outward flow of
combustion gases.
When using a cover plate or exhaust hood: make
sure that the cover does not restrict the flue outlet
and that the cap does not impede the outward flow
of combustion gases.
The chimney must end in a zone that is not
affected by surrounding buildings, adjacent trees or
other obstacles.
The chimney part outside the house must be
insulated.
The chimney must be at least 4metres high.
As a rule of thumb: 60cm above the ridge of the
roof.
If the ridge of the roof is more than 3metres away
from the flue: stick to the measurements in the
following figure. A = the highest point of the roof
within a distance of 3 metres.
Ventilation of the area
For good combustion, the appliance needs air
(oxygen). That air is supplied via adjustable air inlets
from the area where the appliance is installed.
The combustion will be incomplete in case of
insufficient ventilation, which results in toxic
gases being produced and spread through the
area.
As a rule of thumb, the air supply should be
5.5cm²/kW. Extra ventilation is needed when:
The appliance is in an area that is well insulated.
There is mechanical ventilation, for example a
central extraction system or an extraction hood in
an open kitchen.
You can provide extra ventilation by having a
ventilation louvre installed in the outside wall.
Make sure that other air consuming appliances (such
as tumble-driers, other heating appliances or a bath
room fan) have their own supply of outside air, or are
switched off when you use the appliance.
You can also connect the appliance to a supply
of outside air. For this purpose, a connecting
kit has been included. Extra ventilation is not
needed in that case.
Subject to change because of technicalimprovements
5
35


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dovre 2180CBS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dovre 2180CBS in the language / languages: English, German, Dutch, French, Italian, Spanish as an attachment in your email.

The manual is 30,24 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info