1 Important Information
During start-up, observe the respective national safety
regulations and the applicable VDE safety regulations,
particularly VDE 0100, as well as the technical connection
requirements of the utility companies (EVU) and network
operators!
The heat pump controller should only be operated in dry
rooms with temperatures ranging between 0 °C and 35 °C.
Ensure that no condensation forms on the device.
All sensor connecting cables with a conductor cross-section
of 0.75 mm² can be extended to a maximum of 40 m.
Sensor leads should not be installed next to power cables.
To ensure that the frost protection function of the heat pump
works properly, the heat pump controller must remain
connected to the power supply and the flow must be
maintained through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal
resistance of the measuring instrument, a voltage can also
be measured when the contacts are open. However, this will
be much lower than the mains voltage.
Terminals J1 to J11, J20, J21, J23 and the terminal strip X3
of the N1 heating controller are connected to an extra-low
voltage supply. Terminals J1 to J4, J9 to J10 and the
terminal strip X3 of the N17 cooling modul are connected to
an extra-low voltage supply. If, due to a wiring error, the
supply voltage is mistakenly connected to these terminals,
the heat pump controller will be destroyed.
2 Heat Pump Manager: Scope of Supply
The heat pump manager is available in three versions.
Integrated in the heat pump casing
Wall-mounted heat pump manager
for a heat pump heating system
Wall-mounted heat pump manager
for a heat pump system for heating and cooling (Chap. 5 on
p. 8).
The scope of supply of the wall-mounted heat pump manager
includes:
Heat pump manager with casing
3 dowels (6 mm) with screws for wall mounting
External temperature sensor
Operator's manual and operating instructions for users
Installation and start-up instructions for technicians
3 Installation
3.1 Attaching the wall-mounted heat pump manager (heating)
The controller is attached to the wall with the 3 screws and
dowels (6 mm) included in the scope of supply. The following
mounting procedure should be used to avoid soiling or damaging
the controller:
Mount the dowels for the upper fastening eye at operator
level.
Screw the screw into the dowel so that the controller can be
mounted.
Hang the controller on the upper fastening eye.
Mark the position of the side drill-holes.
Remove the controller.
Mount the dowels for the side drill-holes.
Re-hang the controller and tighten the screws.
Fig. 3.1: Dimensions of the wall-mounted heat pump manager (heating)
16


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex WPM Econ5Plus at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex WPM Econ5Plus in the language / languages: English, German, French as an attachment in your email.

The manual is 1.92 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info