798220
24
Zoom out
Zoom in
Previous page
1/72
Next page
EN-6 452237.66.49a · FD 0108 www.glendimplex.de
English WI 35TU - WI 45TU
7.4 Temperature sensor
The following temperature sensors are already installed or must
be installed additionally:
Outside temperature sensor (R1) supplied (NTC-2)
Return temperature secondary circuit (R2) installed
(NTC-10)
Return temperature primary circuit (R24) installed (NTC-
10)
Flow temperature secondary circuit (R9) installed (NTC-10)
Flow temperature primary circuit (R6) installed (NTC-10)
7.4.1 Sensor characteristic curves
The temperature sensors to be connected to the heat pump
manager must correspond to the sensor characteristic curve il-
lustrated in Fig. 7.2 on page 6. The only exception is the outside
temperature sensor included in the scope of supply of the heat
pump (see Fig. 7.3 on page 6)
Fig. 7.2:Sensor characteristic curve NTC-10
Fig. 7.3:Sensor characteristic curve NTC-2 according to DIN 44574 Out-
side temperature sensor
7.4.2 Mounting the outside temperature
sensor
The temperature sensor must be mounted in such a way that all
weather conditions are taken into consideration and the meas-
ured value is not falsified.
On the external wall of a heated room used as living space,
if possible on the north or north-west side of the building
Do not install in a “sheltered position" (e.g. in a wall niche or
under a balcony)
Not in the vicinity of windows, doors, exhaust air vents, ex-
ternal lighting or heat pumps
Not to be exposed to direct sunlight at any time of year
-
7.4.3 Installing the strap-on sensor
It is only necessary to mount the strap-on sensors if they are in-
cluded in the scope of supply of the heat pump but have not yet
been installed.
The strap-on sensors can be fitted as pipe-mounted sensors or
installed in the immersion sleeve of the compact manifold.
Mounting as a pipe-mounted sensor
Remove paint, rust and scale from heating pipe.
Coat the cleaned surface with heat transfer compound (ap-
ply sparingly).
Attach the sensor with a hose clip (tighten firmly, as loose
sensors can cause malfunctions) and thermally insulate.
Temperature in °C -20 -15 -10 -5 0 5 10
NTC-2 in k14.6 11.4 8.9 7.1 5.6 4.5 3.7
NTC-10 in k67.7 53.4 42.3 33.9 27.3 22.1 18.0
15 20 25 30 35 40 45 50 55 60
2.9 2.4 2.0 1.7 1.4 1.1 1.0 0.8 0.7 0.6
14.9 12.1 10.0 8.4 7.0 5.9 5.0 4.2 3.6 3.1
0
10
20
30
40
50
60
70
-20-15-10-5 0 5 1015202530354045505560
External temperature in [°C]
Resistance value in [kOhm]
0
2
4
6
8
10
12
14
16
18
20
-20-15-10-5 0 5 1015202530354045505560
External temperature in [°C]
Resistance value in [kOhm]
Dimensioning parameter sensor lead
Conductor material Cu
Cable-length 50 m
Ambient temperature 35 °C
Laying system B2 (DIN VDE 0298-4 /
IEC 60364-5-52)
External diameter 4-8 mm
Hose clip
Strap-on sensor
Thermal insulation
24


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex WI 35TU at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex WI 35TU in the language / languages: English, German, French as an attachment in your email.

The manual is 2.76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info