EN-8 452232.66.11 · FD 9206 www.dimplex.de
English
WI 18TE - WI 27TE
7.5 Electrical connection
7.5.1 General
During start-up, observe the respective national safety regula-
tions and the applicable VDE safety regulations, particularly
VDE 0100, as well as the technical connection requirements of
the utility companies (EVU) and network operators!
To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain connected
to the power supply and the flow must be maintained through the
heat pump at all times.
The switching contacts of the output relay are interference-sup-
pressed. Therefore, depending on the internal resistance of the
measuring instrument, a voltage can also be measured when the
contacts are open. However, this will be much lower than the line
voltage.
Extra-low voltage is connected to controller terminals N1-J1 to
N1-J11; N1-J24 and terminal strip X3. If, due to a wiring error,
the line voltage is mistakenly connected to these terminals, the
heat pump manager will be destroyed.
7.5.2 Electrical installation
1) The supply cable for the output section of the heat pump (up
to 4-core) are fed from the electricity meter of the heat pump
via the utility blocking contactor (if required) into the heat
pump (see heat pump operating instructions for supply volt-
age).
Connection of the mains cable to the control panel of the
heat pump via terminal X1: L1/L2/L3/PE.
ATTENTION!
Ensure the rotary field is clockwise when connecting the mains cables (if
the rotary field is not clockwise, the heat pump will not work properly, is
very loud and may cause damage to the compressor).
An all-pole disconnecting device with a contact gap of at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping for
all external conductors must be installed in the power supply
for the heat pump (tripping current and characteristic in com-
pliance with the device information).
2) The three-core supply cable for the heat pump manager
(heating controller N1) is fed into the heat pump . Connec-
tion of the control line to the control panel of the heat pump
via terminal X2: L/N/PE.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a constant voltage. For this reason, it
should be tapped upstream from the utility blocking contac-
tor or be connected to the household current, as important
protection functions could otherwise be lost during a utility
block.
3) The utility blocking contactor(K22) with main contacts and
an auxiliary contact should be dimensioned according to the
heat pump output and must be supplied by the customer.
The NO contact of the utility blocking contactor is looped
from terminal strip X3/G (24VAC) to connector terminal J5/
ID3. CAUTION! Extra-low voltage!
4) The contactor (K20) for the immersion heater (E10) of mono
energy systems (HG2) should be dimensioned according to
the radiator output and must be supplied by the customer. It
is controlled (230 V AC) by the heat pump manager via ter-
minals X2/N and N1-J13/NO4.
5) The contactor (K21) for the flange heater (E9) in the hot
water cylinder should be dimensioned according to the radi-
ator output and must be supplied by the customer. It is con-
trolled (230 V AC) by the heat pump manager via terminals
X2/N and N1-J16/NO 10.
6) The contactors mentioned above in points 3, 4 and 5 are in-
stalled in the electrical distribution system. The mains cables
for the heating elements should be dimensioned and pro-
tected according to DIN VDE 0100.
7) All cables must be installed as permanent wiring.
8) The heat circulating pump (M13) is connected to terminals
X2/N and N1-J13/NO 5.
9) The DHW loading pump (M18) is connected to terminals X2/
N and N1-J13/NO 6.
10) The brine or well pump is connected to terminals 2/4/6 of K5
and PE.
11) The return sensor (R2) is integrated into heat pumps for in-
door installation.
The heat pump manager is connected via the following ter-
minals: X3/GND and N1-J2/B2.
12) The external sensor (R1) is connected to terminals X3/GND
and N1-J2/B1.
13) The domestic hot water sensor (R3) is included with the do-
mestic hot water cylinder and is connected to terminals X3/
GND and N1-J2/B3.
22


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex WI 18 TE at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex WI 18 TE in the language / languages: English, German, French as an attachment in your email.

The manual is 2.24 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Dimplex WI 18 TE

Dimplex WI 18 TE Usermanual and installation guide - Dutch - 32 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info