English WI 140TUR+
tective motor switch at the site must be checked and re-
placed if necessary.
Connection of the well pump mains cable on the heat
pump's control panel via terminal X1: L11/L21/L31/PE.
Ensure that the supply voltage for these terminals cannot
be switched off by the tariff contactor when connecting
the mains cable for the well pump, in order to safeguard
the switch-off delay of the well pump.
12) The return flow sensor is integrated into the heat pumps.
The return flow sensor must be installed in the immersion
sleeve in the manifold only when a dual differential pres-
sureless manifold is used. The single-core wires are then
connected to terminals X3/GND and X3/ R2.1. Bridge A-
R2 (situated between X3/U2 and X3/1 when delivered)
must then be moved to terminals X3/1 and X3/2.
13) The external sensor (R1) is connected to terminals X3/GND
and X3/R1.
14) The domestic hot water sensor (R3) is included with the
domestic hot water cylinder and is connected to terminals
X3/GND and X3/R3.
All lines must be fed into the device from the back and secured
at the switch box using cable connectors. They must addition-
ally be secured with a strain relief.
7.5.3 Connecting an electronically
regulated circulating pump
Electronically regulated circulating pumps have high starting
currents, which may shorten the service life of the heat pump
manager. For this reason, a coupling relay is installed or must be
installed between the output of the heat pump manager and
the electronically regulated circulating pump. This is not neces-
sary if the permissible operating current of 2 A and a maximum
starting current of 12 A are not exceeded in the electronically
regulated circulating pump or if express approval has been is-
sued by the pump manufacturer.
ATTENTION!
!
!
It is not permitted to connect more than one electronically
regulated circulating pump via a relay output.
8Start-Up
8.1 General
To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorised by
the manufacturer. These measures can also include an addi-
tional warranty under certain conditions (see Warranty)
8.2 Preparation
Prior to commissioning, the following items need to be
checked:
All connections of the heat pump must have been made as
described in Chapter 7.
The heat source system and the heating circuit must have
been filled and checked.
The strainer must have been fitted in the well water inlet of
the heat pump.
In the well water and heating circuits all valves that might
impair the proper flow must be open.
The settings of the heat pump controller must be adapted
to the heating installation in accordance with the instruc-
tions contained in the manager's operating manual.
8.3 Procedure
The start-up of the heat pump is effected via the heat pump
manager.
ATTENTION!
!
!
Commissioning is to be effected in accordance with the
installation and operating manual of the heat pump manager.
28


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex WI 140TUR plus at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex WI 140TUR plus in the language / languages: English, German, French as an attachment in your email.

The manual is 2.69 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info