Heating water minimum flow rate
The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating system.
This can be accomplished, for example, by installing a dual dif-
ferential pressureless manifold.
NOTE
º
The use of an overflow valve is only recommended for panel
heating and a max. heating water flow of 1.3 m³/h. System
faults may result if this is not observed.
Provided the heat pump manager and heating circulating
pumps are ready for operation, the frost protection feature of
the heat pump manager is active. If the heat pump is taken out
of service or in the event of a power failure, the system has to be
drained. In heat pump installations where a power failure can-
not be readily detected (holiday house), the heating circuit must
contain a suitable antifreeze product.
7.3 Connection on Heat Source
Side
The following procedure must be observed when making the
connection:
Connect the brine line to the flow and return pipe heat source
of the heat pump.
The hydraulic integration diagram must be observed here.
ATTENTION!
!!
The supplied strainer must be fitted in the heat source inlet of
the heat pump in order to protect the evaporator against the
ingress of impurities.
The brine liquid must be produced prior to charging the system.
The brine concentration must be at least 25 %. Freeze protec-
tion down to -14°C can thus be ensured.
Only antifreeze products on the basis of mono-ethylene glycol
or propylene glycol may be used.
The heat source system must be vented (de-aerated) and
checked for leaks.
ATTENTION!
!!
The brine solution must contain at least 25 % of an antifreeze
agent on a mono-ethylene glycol or propylene glycol basis
and must be mixed prior to filling.
NOTE
º
A suitable de-aerator (micro bubble air separator) must be
installed in the heat source circuit by the customer.
7.4 Temperature sensor
The following temperature sensors are already installed or must
be installed additionally:
External temperature sensor (R1) supplied (NTC-2)
Return temperature secondary circuit (R2) installed (NTC-
10)
Flow temperature secondary circuit (R9) installed (NTC-10)
Flow temperature primary circuit (R6) installed (NTC-10)
7.4.1 Sensor characteristic curves
The temperature sensors to be connected to the heat pump
manager must correspond to the sensor characteristic curve
illustrated in Fig. 7.2. The only exception is the external
temperature sensor included in the scope of supply of the heat
pump (see Fig. 7.3)
Fig. 7.2:Sensor characteristic curve NTC-10
Fig. 7.3:Sensor characteristic curve, NTC-2 according to DIN 44574 Ex-
ternal temperature sensor
Temperature in °C -20 -15 -10 -5 0 5 10
NTC-2 in k14.6 11.4 8.9 7.1 5.6 4.5 3.7
NTC-10 in k67.7 53.4 42.3 33.9 27.3 22.1 18.0
15 20 25 30 35 40 45 50 55 60
2.9 2.4 2.0 1.7 1.4 1.1 1.0 0.8 0.7 0.6
14.9 12.1 10.0 8.4 7.0 5.9 5.0 4.2 3.6 3.1
0
10
20
30
40
50
60
70
-20-15-10-5 0 5 1015202530354045505560
External temperature in [°C]
Resistance value in [kOhm]
0
2
4
6
8
10
12
14
16
18
20
-20-15-10-5 0 5 1015202530354045505560
External temperature in [°C]
Resistance value in [kOhm]
23


Need help? Post your question in this forum.

Forumrules
1

Forum

dimplex-sih-20te

Reset search

  • The manual says there is a modbus and ethernet option. Is there a list of modbus registers available? Submitted on 14-1-2022 at 12:40

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex SIH 20TE at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex SIH 20TE in the language / languages: English, German, French as an attachment in your email.

The manual is 1.92 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Dimplex SIH 20TE

Dimplex SIH 20TE Usermanual and installation guide - Dutch - 24 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info