798435
31
Zoom out
Zoom in
Previous page
1/72
Next page
www.glendimplex.de 452237.66.55 · FD 0007 EN-11
SI 50 - 70 TUR English
7.6 Electrical connection
7.6.1 General
All electrical installation work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the
installation and operating instructions,
country-specific installation regulations (e.g. VDE 0100),
technical connection conditions of the energy suppliers
and supply grid operators (e.g. TAB) and
local conditions.
To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain con-
nected to the power supply and the flow must be maintained
through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal resistance of
the measuring instrument, a voltage can also be measured
when the contacts are open. However, this will be much lower
than the line voltage.
Extra-low voltage is applied on the controller terminals N1-J1 to
N1-J11; N1-J19; N1-J20; N1-J23 to N1-J26; N17-J1 to N17-
J4; N17-J9; N17-J10; N0-J2 to N0-J14 and the terminal strips
X3 and X5.1. If, due to a wiring error, the line voltage is mistak-
enly connected to these terminals, the heat pump manager will
be destroyed.
7.6.2 Electrical installation work
1) The 4-core electrical supply cable for the output section of
the heat pump is fed from the heat pump meter via the util-
ity company blocking contactor (if required) into the heat
pump.
Connection of the mains cable to the contact plate of the
heat pump via terminals X1: L1/L2/L3/PE.
An all-pole disconnecting device with a contact gap of at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping
for all external conductors must be installed in the power
supply for the heat pump (tripping current and characteris-
tic in compliance with the device information).
CAUTION!
!
!
Ensure the rotary field is clockwise when connecting the
mains cables (if the rotary field is not clockwise, the heat
pump will not work properly, is very loud and may cause
damage to the compressor).
2) The 3-core electric supply cable for the heat pump man-
ager (heating controller N1) is fed into the heat pump.
Connection of the control cable to the contact plate of the
heat pump via terminal X2: L/N/PE.
Details on the power consumption of the heat pump are
listed on both the product information sheet and the type
plate.
The supply cable (L/N/PE~230 V, 50 Hz) for the heat pump
manager must have a continuous voltage. For this reason,
it should be tapped upstream from the utility blocking con-
tactor or be connected to the household current, because
otherwise important protection functions could be lost
during a utility block.
3) The utility blocking contactor (K22) with 3 main contacts
(1/3/5 // 2/4/6) and an auxiliary contact (NO contact 13/
14) should be dimensioned according to the heat pump
output and must be supplied on-site.
The NO contact of the utility blocking contactor (13/14) is
looped from terminal strip X3/G to controller N1/J5-ID3.
CAUTION! Extra-low voltage!
4) The contactor (K20) for the immersion heater (E10) of
mono energy systems (HG 2) should be dimensioned ac-
cording to the radiator output and must be provided on-
site. It is controlled (230 V AC) from the heat pump man-
ager via terminals X2/N and contact N1/J13-NO4 on the
heat pump manager.
5) The contactor (K21) for the flange heater (E9) in the do-
mestic hot water cylinder should be dimensioned accord-
ing to the radiator output and must be provided on-site. It
is controlled (230 V AC) from the heat pump manager via
terminals X2/N and contact N1/J16-NO10.
6) The contactors mentioned above in points 3, 4 and 5 are
installed in the electrical distribution system. Mains cables
for installed heating systems must be designed and pro-
tected in accordance with the valid standards and regula-
tions.
7) All installed electric cables must have permanent wiring.
8) The heat circulating pump (M13) is activated via the con-
tact N1-J13/NO5. Connection points for the pump are
coupling relays KM13/14 and X2/N.
9) The auxiliary circulating pump (M16) is activated via the
contact N1-J16/NO9. Connection points for the pump are
coupling relays KM16/14 and X2/N.
10) The domestic hot water circulating pump (M18) is acti-
vated via the contact N1-J13/NO6. Connection points for
the pump are coupling relays KM18/14 and X2/N.
11) The brine or well pump (M11) is activated via the contact
refrigeration circuit controller N0/J18-Out3. A coupling
relay is already integrated in this output. If an additional
well pump is used, the protective motor switch at the site
must be checked and replaced if necessary.
Ensure that the power supply for these terminals cannot be
switched off by the tariff contactor when connecting the
mains cable for the well pump, in order to safeguard the
switch-off delay of the well pump.
12) A return sensor is integrated into the heat pumps. The de-
mand sensor must be installed in the immersion sleeve in
the manifold only when a dual differential pressureless
manifold is used. The single-core wires are then connected
to terminals X3/GND and controller N1/J2-U2.
13) The external sensor (R1) is connected to terminals X3/GND
and controller N1/J2-U1.
14) The domestic hot water sensor (R3) is included with the
domestic hot water cylinder and is connected to terminals
X3/GND and controller N1/J2-U3.
15) The connector cable (or the connector) of the hydraulic 4-
way reversing valve must be connected to the receptacle
of the device mounted at the "top" in the rear wall.
31


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex SI 70TUR at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex SI 70TUR in the language / languages: English, German, French as an attachment in your email.

The manual is 7.41 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info