798458
15
Zoom out
Zoom in
Previous page
1/48
Next page
www.dimplex.de E-5
English
8.3
For more detailed instructions concerning the connection and
functioning of the heat pump controller (e.g. the supplied external
wall sensor) please refer to the enclosed operating manual of the
controller.
An automatic circuit-breaker with simultaneous tripping of all ex-
ternal conductors is to be provided in the load power supply. The
circuit-breaker must be an all-pole disconnect device with a con-
tact gap of at least 3 mm. The same applies to any additional dis-
able contactors that may be required, e.g. during shut-off periods
imposed by the utility company. The required cross-sectional
area of the conductors is to be selected according to the power
consumption of the heat pump, the technical connection require-
ments of the relevant utility company and all applicable regula-
tions. Power consumption data of the heat pump is provided in
the product literature and on the nameplate. The terminals are
designed for a max. conductor cross-section of 35 mm².
ATTENTION!
The clockwise phase sequence must be observed when connecting the
load lines (the heat pump will deliver no output and will be very noisy
when the phase sequence is incorrect).
The power cable must be run through the guide tubes, inserted
into the side of the control box and secured by means of the
strain relief.
8 Commissioning
8.1 General Information
To ensure proper commissioning it should be carried out by a
customer service authorised by the manu-facturer. This will lead,
under certain circumstances, to an extension of the warranty pe-
riod (cf. Warranty).
8.2 Preparatory Steps
Prior to commissioning, the following items need to be checked:
All connections of the heat pump must have been made as
described in Chapter 7.
The heat source system and the heating circuit must have
been filled and checked.
The strainer must have been fitted in the sole inlet of the
heat pump.
In the brine and heating circuits all valves that might impair
the proper flow must be open.
The settings of the heat pump controller must be adapted to
the heating installation in accordance with the instructions
contained in the controller's operating manual.
8.3 Commissioning Procedure
The start-up of the heat pump is effected via the heat pump con-
troller.
ATTENTION!
Commissioning is to be effected in accordance with the installation and
operating manual of the heat pump controller.
Where an overflow valve is fitted to assure the minimum heating
water flow rate, the valve must be set in accordance with the re-
quirements of the heating installation. An incorrect setting may
result in various error symptoms and an increased elec-tric
power consumption. To correctly set the overflow valve, the fol-
lowing procedure is recommended:
Close all of the heating circuits which may also be closed during
operation (depending on the type of heat pump usage) so that
the least favourable operating state - with respect to the water
flow rate - is achieved. Normally, these heating circuits are those
of the rooms located on the south and west sides of buildings. At
least one heating circuit must remain open (e.g. bathroom).
The overflow valve is to be opened to such an extent that based
on the current heat source temperature the maximum tempera-
ture difference between heating supply and return flow tempera-
ture is obtained, as indicated in the table below. The tempera-
ture difference should be measured as closely to the heat pump
as possible. In mono-energetic systems, the electric heating ele-
ment is to be deactivated.
Any malfunctions occurring during operation are displayed on the
heat pump controller and can be corrected as described in the
operating manual of the heat pump controller.
Heat source
temperature max. difference between heating
supply and return temperature
from to
-5° C 0° C 10 K
1° C 5° C 11 K
6° C 9° C 12 K
10° C 14° C 13 K
15° C 20° C 14 K
21° C 25° C 15 K
15


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex SI 100ZS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex SI 100ZS in the language / languages: English, German, French as an attachment in your email.

The manual is 2.58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info