EN-6 452161.66.22 · FD 9912 www.gdts.one
English LI 20TES - LI 28TES
6Set-UP
6.1 General Information
The air-to-water heat pump must be installed in a frost-free,
dry room on an even, smooth and horizontal surface. The entire
base of the frame should lie directly on the floor to ensure an
adequate soundproof seal. T If this is not the case, additional
sound insulation measures may be necessary. If the device is
installed on top of a built-under buffer tank, a surface that fully
supports the base is required. The heat pump must be installed
so that maintenance work can be carried out without being hin-
dered. This is ensured if the clearance displayed below is main-
tained.
Never install the device in rooms subject to high humidity. Con-
densation can form on the heat pump and air circuit if the hu-
midity exceeds 50% and the external temperature is below
C.
Neither frost nor temperatures higher than 35 °C must occur in
the installation location at any time of the year.
If the heat pump is installed on an upper storey, the load-bear-
ing capacity of the ceiling should be checked. On account of
the acoustics, measures for isolating possible vibrations should
also be very carefully planned in advance as well. Installation on
a wooden floor is not recommended.
6.2 Condensed Water Pipe
Condensate that forms during operation must be drained off
frost-free. To ensure proper drainage, the heat pump must be
mounted horizontally. The condensate pipe must have a mini-
mum diameter of 50 mm and must be fed into a sewer in such
a way that it is safe from frost. Do not discharge the condensate
directly into clearing tanks or cesspits, as aggressive vapours or
a condensed water pipe which has not been laid in a frost-free
manner could destroy the evaporator.
6.3 Sound
To prevent solid-borne sound from being transmitted to the
heating system, we recommend connecting the heat pump to
the heating system using a flexible hose.
Installed air ducts should be sound-isolated from the heat
pump to prevent the transmission of solid-borne sound to the
ducts.
7 Installation
7.1 General Information
The following connections need to be established on the heat
pump:
Fresh and exhaust air
Flow and return flow of the heating system
Condensate outflow
Temperature sensor
Voltage supply
7.2 Air Connection
7.2.1 Air Connection General Information
ATTENTION!
!
!
Do not restrict or block the area around the air intake or outlet.
ATTENTION!
!!
Only operate the heat pump with the air ducts connected.
The glass fibre reinforced concrete air ducts offered as acces-
sories are moisture-resistant and diffusion-free.
The sealing collar is used to seal the air ducts on the heat pump.
The air ducts are not screwed directly onto the heat pump. Only
the rubber seal comes into direct contact with the heat pump
when the system is installed correctly. This guarantees easy as-
sembly and disassembly of the heat pump and also ensures
that solid-borne sound is well insulated.
If another type of air duct is used, observe the external and in-
ternal dimensions as specified in the figure. Also ensure that the
vibration and duct insulation are adequate.
If flange-mounted air ducts are used, connecting stubs are se-
cured on the air inlet and air outlet sides of the evaporator with
4 M8x16 hexagon bolts in the threaded holes provided. When
doing this, ensure that both air duct stubs only touch the insu-
lation. There should be no contact with the external sheeting.
0,6 m
1m
0,2 m
0,6 m
26


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex LI 28TES at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex LI 28TES in the language / languages: English, German, French as an attachment in your email.

The manual is 2.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info