EN-16 452162.66.09a · FD 0108 www.glendimplex.de
English LAK 3IMR - LAK 14ITR
8.4 Characteristic curve temperature sensor outdoor unit
8.5 Characteristic curve temperature sensor indoor unit
8.5.1 Sensor characteristic curves
The temperature sensors to be connected to the heat pump
manager must correspond to the sensor characteristic curve il-
lustrated in Fig.8.1 on pag. 16. The only exception is the out-
door temperature sensor included in the scope of supply of the
heat pump (see Fig.8.2 on pag. 16)
Fig. 8.1: Sensor characteristic curve NTC-10
Fig. 8.2: Sensor characteristic curve NTC-2 according to DIN 44574
Outdoor temperature sensor
8.5.2 Mounting of the external outside
temperature sensor (optional)
With outside temperature based control, the connection of an
outside temperature sensor (FG 3115) is recommended for
mounting on the north side of the building, as incorrect values
would otherwise be recorded for the heating curve calculation
(e.g. during intensive sun radiation).
The external sensor (FG3115) is connected to the heat pump
manager and activated by after-sales service during commis-
sioning.
With room temperature based control via the smart RTC, no ad-
ditional outside temperature sensor is required.
-
NTC - 10 Air sensor (outdoor unit)
Temperature in °C -20 -15 -10 -5 -2 0 2 5 10 15 18 20 22 24
k105 80.2 58.2 44.0 37.4 33.6 30.3 25.9 20.2 15.8 13.8 12.5 11.4 10.5
Temperature in °C 25 26 28 30 32 34 36 38 40 50 60 70 80 90
k10.0 9.57 8.76 8.04 7.38 6.78 6.24 5.74 5.30 3.59 2.49 1.76 1.27 0.93
NTC - 5 Pipe-mounted sensors (outdoor unit)
Temperature in °C -20 -15 -10 -5 -2 0 2 5 10 15 18 20 22 24
k52.7 38.9 29.1 22.0 18.7 16.8 15.1 13.0 10.1 7.92 6.88 6.27 5.72 5.23
Temperature in °C 25 26 28 30 32 34 36 38 40 50 60 70 80 90
k5.00 4.78 4.38 4.02 3.69 3.39 3.12 2.87 2.65 1.79 1.24 0.88 0.64 0.47
NTC - 200 Hot gas sensor (output compressor)
Temperature in °C 1 5 10 15 20 25 30 35 40 45 50 55 60 65
k525.00 448.00 326.00 294.33 242.20 200.00 167.57 138.03 133.80 98.00 82.00 64.50 59.00 50.71
Temperature in °C 70 75 80 85 90 95 100 105 110 115 120 130
k43.73 37.35 32.20 28.16 24.60 21.37 18.50 16.60 14.50 13.30 12.80 10.80
Temperature in °C -20 -15 -10 -5 0 5 10
NTC-2 in k14.6 11.4 8.9 7.1 5.6 4.5 3.7
NTC-10 in k67.7 53.4 42.3 33.9 27.3 22.1 18.0
15 20 25 30 35 40 45 50 55 60
2.92.42.01.71.41.11.00.80.70.6
14.9 12.1 10.0 8.4 7.0 5.9 5.0 4.2 3.6 3.1
0
10
20
30
40
50
60
70
-20-15-10-5 0 5 1015202530354045505560
External temperature in [°C]
Resistance value in [kOhm]
Dimensioning parameter sensor lead
Conductor material Cu
Cable-length 50 m
Ambient temperature 35 °C
Laying system B2 (DIN VDE 0298-4 /
IEC 60364-5-52)
External diameter 4-8 mm
0
2
4
6
8
10
12
14
16
18
20
-20-15-10-5 0 5 1015202530354045505560
External temperature in [°C]
Resistance value in [kOhm]
42


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex LAK 14IMR at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex LAK 14IMR in the language / languages: English, German, French as an attachment in your email.

The manual is 7.79 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info