De Dietrich Gas 310/610 ECO

Fan not operating
- Fan defective
- Fan cable is corroded, resulting in absence of voltage or control signal.

Fan operates continuously or signal
incorrect
- Check the fan cable connectors on both the fan and the automatic burner unit
side.
- Fan electronics defective
- Excessive negative chimney pressure

Max ΔT exceeded
Check;
- Flow
- System as has proper air elimination
- Water pressure in the system

Temperature sensor fault Short circuit of flow temperature sensor

Temperature sensor fault Short circuit of return temperature sensor

Temperature sensor fault Short circuit of flue gas temperature sensor

Temperature sensor fault Flow temperature sensor not connected or defective

Temperature sensor fault Return temperature sensor not connected or defective

Air pressure differential sensor short
circuited
- Check the connecting cable of the air pressure differential sensor
- Air pressure differential sensor is defective or not connected

Air pressure differential sensor open
- Check the air pressure differential sensor connecting cable for short circuiting,
etc.
- Air pressure differential sensor is defective

Temperature sensor fault Flue gas temperature sensor not connected or defective

one or more parameters are out of limits The input of the parameter(s) are incorrect

Hydraulic pressure sensor short circuited
- Check the hydraulic pressure sensor connecting cable for short circuit, etc...
- Hydraulic pressure sensor is defective

Hydraulic pressure sensor open
- Check connecting cable of the hydraulic pressure sensor for short circuit, etc...
- The hydraulic pressure sensor is defective or not connected

Maximum flue gas temperature
exceeded
Check the heat exchanger for fouling on the flue gas side

Air pressure differential sensor not
opening
Check;
- Is the air pressure differential sensor defective
- Has the wiring been short circuited
- Excessive positive chimney pressure

Weak flame ionization signal during
operation (after 4 restarts during 1 heat
demand)
- Flue gas recirculation, check venting & heat exchanger for leaks
- Insufficient air flow due to blockage
- Check the boiler settings

Boiler block temperature too high
Check; The heating pump is operating
- There is sufficient water flow through the boiler
- The water pressure is > 11 psi or 0.8 bar

Gas leak VA1 (optional)
The VPS gas leakage control has detected a leak, Check for external leaks,
otherwise replace gas valve multiblock

Gas leak VA2 (optional)
The VPS gas leakage control has detected a leak, Check for external leaks,
otherwise replace gas valve multiblock

Air pressure differential sensor fault
Air pressure differential sensor fault during pre-purge (after 4 restarts)
Check; Is the air pressure differential sensor defective
- Has the wiring short circuited
- Excessive high positive chimney pressure

Boiler block temperature > flow
temperature + hysteresis
Check; - The heating pump is operating
- There is sufficient water flow through the boiler
- The water pressure is < 11 psi or 0.8 bar

Temperature sensor fault Short circuit of boiler block sensor

Temperature sensor fault Boiler shut-off sensor is not connected or defective

Boiler block temperature too high
Check; - The heating pump is operating
- There is sufficient water flow through the boiler
- The water pressure is < 11 psi or 0.8 bar
other
codes
Control unit has internal fault
Proceed as follows with all non-listed codes
- Press the reset button once
- Check that the wiring is not short circuited
- If the fault persists, contact our service department
Table 23 Failure codes
WARNING!! Do not reset the boiler control until you can identify and have resolved the problem. Unresolved problems
could cause personal injury or damage to the boiler and controls.
61


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for De Dietrich Gas 610 ECO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of De Dietrich Gas 610 ECO in the language / languages: English as an attachment in your email.

The manual is 3,76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info