52 Mounting and installation work
5.5.2 Notes on water installation
Water supply
The water supply is to be carried out according to the gure found in chapter 5.5.1 and the applicable
local regulations for water installations. The indicated connection specications must be observed.
The installation of the lter valve (accessory "Z261", alternatively a shut-off valve and a 5 µm water
lter can be used) should be made as close as possible to the steam humidier.
Note: on large units with two steam cylinders, on double units and on Linkup systems each unit
must be connected separately via a lter valve (or shut-off valve and water lter) to the water supply.
Admissible water supply pressure:
1.0…10.0 bar (units without drain water cooling)
2.0…10.0 bar (units with drain water cooling)
Note: the supply water system must be hammer-free. For mains pressures >10 bar, the connection
must be made via a pressure reducing valve (adjusted to 2.0 bar). For mains pressures <1.0 bar
(units without drain water cooling) <2.0 bar (units with drain water cooling) please contact your
Condair supplier.
Notes on water quality:
For the water supply of the Condair RS, use exclusively untreated drinking water, water from
RO system or de-ionized water.
The use of additives such as corrosion inhibitors, disinfectants, etc. is not allowed, since these
additives may endanger health and affect proper operation.
The connection material must be pressure-proof and certied for use in drinking water systems.
Important! Before connecting the water line, the line must be well ushed out.
CAUTION!
The thread at the humidier connection is made of plastic. To avoid overtightening, the union nut
of the water pipe must be tightened by hand only.
Water drain
The water drain is to be carried out according to the gures found in chapter 5.5.1 and the applicable
local regulations for water installations. The indicated connection specications must be observed.
Make sure that the drain pipes, the funnel(s) and the siphon(s) are correctly xed and easily acces-
sible for inspections and cleaning purposes.
The draining temperature is: 80…90 °C (with optional drain water cooling <60°C). Use temperature-
resistant installation materials only!
Always lead the supplied drain hose from the connector to the left down to the funnel (see Fig. 21).
On large units with two steam cylinders each drain line must be led into a separate funnel with trap
(see Fig. 22).
On double unit the drain hoses must be connected with hose clamps to a collector with constant
downslope (min. 15 %/8.5°). The drain of the collector must be led with constant downslope (min.
15 %/8.5°) into a funnel with trap (see Fig. 23). The funnel must be positioned with a lateral off-set
to the left side of the unit, to prevent damage to humidier due to rising steam.
Attach drain line(s) in such a way, that it/they cannot slip out of the funnel(s) and that it/they cannot
bottom out in the funnel(s).
The open end of the drain line(s) must not touch the funnel(s) (min. air gap 2 cm).
52


Need help? Post your question in this forum.

Forumrules
1

Forum

condair-rs

Reset search

  • why drain hose led to left, is it due to electrical on right side.
    Submitted on 29-8-2022 at 23:32

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Condair RS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Condair RS in the language / languages: English as an attachment in your email.

The manual is 7,04 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Condair RS

Condair RS User Manual - English - 80 pages

Condair RS User Manual - Dutch - 80 pages

Condair RS Installation Guide - Dutch - 76 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info