37Installation
4.6.3 Installation work
Note: for the connection of the available options please refer to the installation and operation manual
of the corresponding option.
Control signal (Y)
Note: the control settings must be done via the control software of the Condair ME Control. Please
refer to the operation manual of the Condair ME Control.
X16
JP5: 10V
JP4: 24V
B7
24 V
TMP
GND
HUM
24V E
Enable
P/PI
24 V
rh
24 V - voltage supply
Control unit
External continuous humidity or temperature con-
troller
An external continuous humidity or temperature controller
is to be connected to the contacts “HUM” (+) and “GND”
(–) of the terminal block “X16” on the driver board in ac-
cordance with the wiring diagram. The admissible signal
values can be found in the technical data table in the
operation manual. The connecting cable must either be
fed through the rectangular cable feed through or a free
cable gland into the control unit.
Note: If 24V supply is used for the external controller
Jumper “JP4: 24V” must be set and Jumper “JP5: 10V”
must be removed.
The shielding of the control signal must be connected
to terminal “GND”.
Caution! If the shielding of the control signal is already
connected to a po ten tial or a grounded conductor,
do not connect it to terminal “GND”.
X16
JP5: 10V
JP4: 24V
Y
B7
HUM
24/10V
TMP
GND
HUM
24V E
Enable
24 V
rh
24 V - voltage supply
Control unit
Humidity sensor
A humidity sensor is to be connected to the contacts
“HUM” (+) and “GND” (–) of the terminal block “X16” on
the driver board. The admissible signal values can be
found in the technical data table in the operation manual.
The connecting cable must either be fed through the
rectangular cable feed through or a free cable gland
into the control unit.
Note: If 24V supply is used for the external controller
Jumper “JP4: 24V” must be set and Jumper “JP5: 10V”
must be removed.
The shielding of the control signal must be connected
to terminal “GND”.
Caution! If the shielding of the control signal is already
connected to a po ten tial or a grounded conductor,
do not connect it to terminal “GND”.
37


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Condair ME Control at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Condair ME Control in the language / languages: English as an attachment in your email.

The manual is 4,3 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info