28 Mounting and installation work
The installation location of the Condair EL depends largely on the location of the steam distributor (see
chapter chapter 5.4.2). To ensure proper functioning of the steam humidier and to obtain an optimal
efciency, the following points must be considered and observed when choosing the location for the
steam humidier:
Install the steam humidier so that:
the length of the steam line is kept as short as possible (max. 4 m),
the minimum bend radius for steam hoses (R= 300 mm) and of xed pipes (5 x internal
diameter) is maintained,
the upslope and downslope (min. 15 %/8.5°) of the steam hose is maintained.
The Condair EL is designed for wall-mounting in protected interiors. Make sure that the construction
(wall, pillar, oor-mounted console, etc.) to which the humidier is to be mounted, offers a suf-
ciently high load-bearing capacity (take notice of the weight information found in the dimensions
and weights table), and is suitable for the installation.
CAUTION!
Do not mount the steam humidier directly to the ventilation duct (insufcient stability).
The back panel of the Condair EL retains heat during operation (max. surface temperature of the
metal housing approx. 60 - 70 °C). Make sure, therefore, that the construction (wall, pillar, etc.) to
which the unit is to be mounted, does not consist of heat-sensitive material.
Install the Condair EL in such a manner that it is freely accessible with sufcient space available
for maintenance purposes. The minimum distances shown in Fig. 9 must be maintained.
In order to use the cables supplied with double units and Linkup systems, the unit must be mounted
on the same height, with a maximum distance between the units of 50 mm and in the order shown
in Fig. 9.
The Condair EL is protected according to IP20. Make sure the unit is installed in a drip-proof location
and the admissible ambient conditions are complied with.
Do not mount the Condair EL to hot or very cold walls or near vibrating components.
The steam humidier Condair EL must only be installed in rooms with a oor drain.
CAUTION!
If for some reason the Condair EL must be installed in a location without oor drain, it is manda-
tory to provide a leakage monitoring device to safely interrupt the water supply in case of leakage.
When mounting the Condair EL use only the mounting materials supplied with the unit. If mount-
ing with the materials supplied is not possible in your particular case, select a method of mounting
that is of similar stability.
The Condair EL is designed for installation and operation within buildings (admissible temperature
range 5...40 °C). For outdoor operation the Condair EL must be placed in a weather protective hous-
ing. If ambient temperatures near or below the freezing point are expected, the protective housing
must be equipped with thermostat controlled heating of sufcient capacity. The water supply pipe
must be equipped with trace-heating and must be insulated up to the protective housing. The instal-
lation of a normally open valve inside the building envelope that will drain water in case of power
failure is highly recommended.
28


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Condair EL at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Condair EL in the language / languages: English as an attachment in your email.

The manual is 4,71 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Condair EL

Condair EL User Manual - English - 80 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info