IRIS Touch Range Dialler Installation Manual for EN54-21 Fire Applications V1.1 Page 3
October 2013
3. Installation, Configuration and
Commissioning
3.1. Requirements for the monitoring centre
The monitoring centre should set up the monitoring of the site as follows:
Type 1 (i.e. transmission over Ethernet and/or GPRS):
Reporting time (i.e. poll period + poll overdue period) 80s or less.
Type 2 (i.e. PSTN used as main or backup transmission path)
Reporting time (i.e. poll period + poll overdue period) = 24 hours or
less
The IRIS Secure Apps system at the monitoring centre should be set so
that the diallers use the same TCP/IP port number for both alarm
transmission and polling. This setting is found in the System Settings App
under Global Settings > Polling Connections.
3.2. Requirements for the installation
General installation instructions are provided in the installation guides provided
with each product. The following additional requirements are for EN54-21
compliance:
The Fire CIE must have the capability of indicating fire signal
acknowledgements and fault conditions as visual indications driven by the
outputs from the dialler, as described below. These indicators must be in
compliance with EN54-21.
The dialler should be powered from an EN54-4 compliant power source.
The dialler must be mounted in an Access Level 3 protected enclosure
compliant with the requirements of either EN54-2 (Fire detection and fire
7


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Chiron IRIS Touch - Dialler EN54 - 21 Compliant Fire Applications at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Chiron IRIS Touch - Dialler EN54 - 21 Compliant Fire Applications in the language / languages: English as an attachment in your email.

The manual is 0,32 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info