9.3. ELECTRICAL NETWORKS ALLOWED
The following types of distribution network are managed:
Distribution
network Abbreviation Phase
order Remarks Reference
diagram
Single-phase
(single-phase
2-wire)
1P- 2W No The voltage is measured between L1 and N.
The current is measured on the L1 conductor. See § 4.1.1.
Two-phase
(split-phase
single-phase
3-wire)
1P-3W No
The voltage is measured between L1, L2 and N.
The current is measured on the L1 and L2 conductors.
The neutral current is calculated: iN = i1 + i2
See § 4.1.2.
Three-phase,
3-wire D
[2 current sensors]
3P-3WD2
Yes
The power measurement method is based on the two-
wattmeter method with a virtual neutral.
The voltage is measured between L1, L2 and L3.
The current is measured on the L1 and L3 conductors. The
current I2 is calculated (no current sensor on L2): i2 = -i1 -i3
The neutral is not available for the measurement of the
current and of the voltage
See § 4.1.3.1.
Three-phase,
3-wire open D
(2 current sen-
sors)
3P-3WO2 See § 4.1.3.3.
Three-phase
3-wire wye
[2 current sensors]
3P-3WY2 See § 4.1.3.5.
Three-phase,
3-wire D (3 current
sensors) 3P-3WD3
Yes
The power measurement is based on the three-wattmeter
method with a virtual neutral.
The voltage is measured between L1, L2 and L3.
The current is measured on the L1, L2 and L3 conductors.
The neutral is not available for the measurement of the
current and of the voltage
See § 4.1.3.2.
Three-phase,
3-wire open
D (3 current
sensors)
3P-3WO3 See § 4.1.3.4.
Three-phase,
3-wire, wye [3
current sensors]
3P-3WY3 See § 4.1.3.6.
Three-phase,
3-wire D, balanced 3P-3WDB No
The power measurement is based on the one-wattmeter
method.
The voltage is measured between L1 and L2.
The current is measured on the L3 conductor.
U23 = U31 = U12.
I1 = I2 = I3
See § 4.1.3.7.
Three-phase
4-wire wye 3P-4WY Yes
The power measurement is based on the three-wattmeter
method with neutral.
The voltage is measured between L1, L2 and L3.
The current is measured on the L1, L2 and L3 conductors.
The neutral current is calculated: iN = i1 + i2 + i3.
See § 4.1.4.1.
Three-phase,
4-wire, wye,
balanced
3P-4WYB No
The power measurement is based on the one-wattmeter
method.
The voltage is measured between L1 and N.
The current is measured on the L1 conductor.
V1 = V2 = V3
U23 = U31 = U12= V13.
I1 = I2 = I3
IN = 3 x I1
See § 4.1.4.2.
Three-phase,
3-wire, wye 2½ 3P-4WY2 Yes
This method is called the 2½-element method
The power measurement is based on the three-wattmeter
method with a virtual neutral.
The voltage is measured between L1, L3 and N.
V2 is calculated: v2 = - v1 - v3, u12 = 2v1 + v3,
u23= - v1 - 2v3. V2 is assumed to be balanced.
The current is measured on the L1, L2 and L3 conductors.
The neutral current is calculated: iN = i1 + i2 + i3.
See § 4.1.4.3.
70


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Chauvin Arnoux PEL105 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Chauvin Arnoux PEL105 in the language / languages: English as an attachment in your email.

The manual is 11,67 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info