CHIMNEY
HEARTH AND FIRE SURROUND
In order for the appliance to perform satisfactorily the chimney height
must not be less than 4 metres measured vertically from the outlet of
the stove to the top of the chimney. The internal dimensions of the
chimney should preferably be 150-200 mm (6"- 8") either square or
round and MUST NOT BE LESS THAN 125 mm (5") - Arc 5, 150
mm (6") - Arc 7.
If an existing chimney is to be used it must be swept and checked, it
must be in good condition, free from cracks and blockages, and
should not have an excessive cross sectional area. If it was previously
used by an open fire then the chimney should be swept one month
after installation to clear any soot falls which may have occurred due
to the difference in combustion between the stove and the open fire.
If you find that the chimney is in poor condition then expert advice
should be sought regarding the necessity of having the chimney lined.
If it is found necessary to line the chimney then a lining suitable for
Solid Fuel must be used.
If there is no existing chimney then a prefabricated block chimney or
a twin walled insulated stainless steel flue to BSEN 15287-1:2007 can
be used either internally or externally. These chimneys must be fitted
in accordance with the manufacturers instructions and Building
Regulations.
Single wall flue pipe is suitable for connecting the stove to the
chimney but is not suitable for using for the complete chimney. If it is
found that there is excessive draw in the chimney then a draught
stabiliser should be fitted.
It is important that there is sufficient draw in the chimney and that
the chimney does not suffer from down-draught. When the chimney
is warm the draw should be not less than 1.25mm (0.05") water
gauge (12 Pa). If in doubt about the chimney seek expert advice.
The stove must stand on a fireproof hearth and must not be situated
closer than the minimum distance from combustible materials (see
specification table) to the sides or rear above hearth level unless
adequately fireproofed in accordance with local building regulations.
The hearth must be of fireproof material and at least 12mm (1/2in.)
thick. The positioning of the stove and the size of the hearth are
governed by building regulations for Class 1 appliances. These
building regulations state that the hearth must extend in front of the
stove by at least 225mm (9 in.) and to the sides of the stove by at
least 150mm (6 in.). When the fire door is open, it extends beyond
the flat front of the stove by 436mm - Arc 5, 450mm - Arc 7.
If in doubt as to the positioning of the stove, expert advice should be
sought either from the supplier or the local building inspector. The
fireplace must allow good circulation of air around the appliance to
ensure that maximum heat is transferred to the room and also to
prevent the fireplace from overheating. A gap of 150mm (6") each
side and 300mm (12") above the appliance should give sufficient air
circulation. If a wooden mantelpiece or beam is used in the fireplace it
should be a minimum of 460mm (18"), and preferably 600mm (24")
from the appliance. In some situations it may be necessary to shield
11
®
INSTALLATION INSTRUCTIONS
Alternative
Soot Door
Positions
Register Plate
With Soot Door
Register Plate
Soot Door
in side or rear
of Chimney
Fig.7. Vertical register plate with bricked up fireplace
Fig.8. Horizontal register plate with rear flue connection
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Charnwood Arc 7 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Charnwood Arc 7 in the language / languages: English as an attachment in your email.

The manual is 3.22 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Charnwood Arc 7

Charnwood Arc 7 User Manual - French - 23 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info