LET OP: Afhankelijk van het gekozen type unit worden niet alle menu items gebruikt.
4.9.1 - GENUNIT-menu (Algemene parameters)
   
ctrl_typ 0/1/2 - Lokaal = 0. CCN = 1. Afstandsregeling = 2
STATUS Running/O/Stopping/
Delay
- Bedrijfsstatus
ALM Normal/Partial/Shutdown - Alarm status
min_left 0-15 min Startvertraging
HEATCOOL Heat/Cool/Standby/Both - Verwarming/koeling status
LOCAL_HC 0/1/2 - Keuze verwarming/koelbdrijf via de basis-interface
HC_SEL 0/1/2 - Keuze verwarming/koelbdrijf via het CCN netwerk
0 = koeling, 1 = verwarming, 2 = automatisch
LSP_SEL 0/1/2 - Keuze setpoint via de basis-interface
SP_SEL 0/1/2 - Keuze setpoint via het CCN netwerk
0 = Automatisch, 1 = Setpoint1, 2 = Setpoint2
SP_OCC Yes/No - Bezet setpoint actief
CHIL_S_S Enable/Disable - Unit start/stop via het CCN netwerk
CHIL_OCC Yes/No - Unit tijdschema via het CCN netwerk
CAP_T nnn % Totale capaciteit van de unit
CAPA_T nnn % Capaciteit circuit A
CAPB_T nnn % Capaciteit circuit B
DEM_LIM nnn % Capaciteitsbegrenzing
SP ±nnn.n °C Aktieve setpoint
CTRL_PNT ±nnn.n °C Regelpunt
EMSTOP Enable/Emstop - CCN noodstop
4.9.2 - TEMP-menu (Temperaturen)
   
CL_EWT ±nnn.n °C Koeler waterintredetemperatuur
CL_LWT ±nnn.n °C Koeler wateruittredetemperatuur
OAT ±nnn.n °C Buitenluchttemperatuur
CHWSTEMP ±nnn.n °C Gezamenlijke master/slave temperatuur, koeler
HTWSTEMP ±nnn.n °C Gezamenlijke master/slave temperatuur, condensor
DGT A ±nnn.n °C Persgastemperatuur A
SCT_A ±nnn.n °C Verzadigde condensatietemperatuur A
SST_A ±nnn.n °C Verzadigde zuiggastemperatuur A
SUCT_A ±nnn.n °C Zuiggastemperatuur A
DGT_B ±nnn.n °C Persgastemperatuur B
SCT_B ±nnn.n °C Verzadigde condensatietemperatuur B
SST_B ±nnn.n °C Verzadigde zuiggastemperatuur B
SUCT_B ±nnn.n °C Zuiggastemperatuur B
COND_EWT ±nnn.n °C Condensor waterintredetemperatuur
COND_LWT ±nnn.n °C Condensor wateruittredetemperatuur
DRY_LWT ±nnn.n °C Droge koeler wateruittredetemperatuur
4.9.3 - PRESSURE-menu (Drukken koudemiddelcircuit)
   
DP_A ±nnn.n kPa Persdruk A
SP_A ±nnn.n kPa Zuigdruk A
DP_B ±nnn.n kPa Persdruk B
SP_B ±nnn.n kPa Zuigdruk B
4.9.4 - SETPOINT-menu
    
csp1 - 29.7 tot 20 12.0 °C Koel-setpoint 1
csp2 - 29.7 tot 20 12.0 °C Koel-setpoint 2
ice_sp - 29.7 tot 20 12.0 °C Setpoint koeling ijsopslag
hsp1 20 tot 50 50.0 °C Verwarmings-setpoint 1
hsp2 20 tot 50 50.0 °C Verwarmings-setpoint 2
hsp3 20 tot 55 50.0 °C Verwarmings-setpoint 3
hramp_sp 0.1 tot 1.1 0.60 ^C Afkoelsnelheid
cauto_sp 3.9 tot 50 24.0 °C Omschakeling koel-setpoint
hauto_sp 0 tot 46.1 18.0 °C Omschakeling verwarmings-setpoint
lim_sp1 0 tot 100 100 % Limiet-setpoint 1
lim_sp2 0 tot 100 100 % Limiet-setpoint 2
lim_sp3 0 tot 100 100 % Limiet-setpoint 3
cond_sp 30 tot 58 40 °C Setpoint condensatietemperatuur, condensor
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Carrier 30WG at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Carrier 30WG in the language / languages: Dutch as an attachment in your email.

The manual is 0,94 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Carrier 30WG

Carrier 30WG Installation Guide - Dutch - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info