Refrigerant line connection
(Flare connnections)
Collegamento linea refrigerante
(attacchi a cartella)
Refrigerant lines > 4 m:
Add refrigerant for each metre in excess of
this size according to the following table:
Refrigerant charge (g/m)
Diameter 1/4" 5/16" 3/8" 1/2" 5/8" 3/4"
mm 6,35 7,94 9,52 12,7 15,87 19,05
Liquid 15 25 40 75 120 180
Suction —— 614 2 334
After completing the above steps, remove
nut 2 and open the valve completely with
an ALLEN wrench. The valve is closed
before leaving the factory.
Check that there are no refrigerant leaks.
IMPORTANT:
The indications given above refer to
both the suction line and the liquid
line.
Linee di collegamento > 4 m:
Aggiungere fluido refrigerante per ogni
metro aggiuntivo di tubo in funzione delle
dimensioni riportate nella tabella seguente:
Carica refrigerante (gr/m)
Diametro 1/4" 5/16" 3/8" 1/2" 5/8" 3/4"
mm 6,35 7,94 9,52 12,7 15,87 19,05
Liquido 15 25 40 75 120 180
Aspirazione —— 614 2 334
Dopo aver effettuato le suddette operazioni
rimuovere il bocchettone 2 e aprire comple-
tamente la valvola con una chiave a
brugola. La valvola viene fornita chiusa.
Controllare che non ci siano perdite di
refrigerante
IMPORTANTE:
Le indicazioni di cui sopra si riferisco-
no sia alla linea di aspirazione che alla
linea del liquido.
Scelta delle linee frigorifere
Condizioni generali
Nel progettare le linee frigorifere si consiglia
di tenere sempre presente le seguenti
raccomandazioni:
In base alla sistemazione dellunità:
Linea di aspirazione (opzione A):
•È indispensabile un sifone alla base del
tratto verticale
CONDIZIONE MAGGIORMENTE
SFAVOREVOLE: la velocità di aspirazio-
ne nel tratto verticale deve essere
superiore ai 6 m/s
Linea di aspirazione (opzione B):
I sifoni intermedi non sono strettamente
necessari.
CONDIZIONE MAGGIORMENTE
SFAVOREVOLE: La velocità di aspirazio-
ne nel tratto verticale deve essere
superiore ai 6 m/s.
Per entrambi le opzioni (A e B) si deve
ricordare quanto segue:
La velocità massima permessa in ogni
linea è di 15 m/s.
La linea di aspirazione deve essere isolata
e avere una pendenza del 2% verso il
compressore nel tratto orizzontale.
Nei lunghi tratti potrebbe essere necessa-
rio regolare la carica dolio.
Il liquido dovrebbe essere sottoraffredda-
to a una temperatura di almeno 1°C
allorgano di laminazione.
Per questa
ragione, quando la linea di mandata è in
salita e superiore ai 15 m di lunghezza,
deve essere sottoraffreddata di 1°C per
ogni 3.5 m in eccesso.
Unità interna
Unità esterna
Aspirazione
Liquido
A
B
Refrigerant line selection
General conditions
When designing the refrigerant lines, the
following must be kept in mind:
Depending on the unit arrangement:
Suction line (option A):
A trap is needed at the base of the
vertical stretch.
MOST UNFAVOURABLE CONDITION
The suction speed in the vertical stretch
must be higher than 6 m/s.
Suction line (option B):
The intermediate traps can be omitted.
MOST UNFAVOURABLE CONDITION:
The suction speed in the vertical stretch
must be higher than 6 m/s.
For both option A and for option B you must
remember the following:
The maximum speed permitted in any line
is 15 m/s.
The suction line must be insulated and
have a 2% slope towards the compressor
in the horizontal stretch.
In long lengths it could be necessary to
adjust the oil charge.
The liquid should be subcooled by at
least 1 K at the restrictor inlet. If the liquid
line is ariser and longer than 15 m, it must
be subcooled 1 K for each 3.5 m in
excess.
Indoor unit
Outdoor unit
Suction
Liquid
18


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Carrier 07KD at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Carrier 07KD in the language / languages: English, German, French, Italian, Spanish as an attachment in your email.

The manual is 0,56 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info