3.3 SMOKE DUCT SMOKE FITTING
The smoke duct is the pipe that connects the appliance to the flue.
This smoke fitting must comply in particular with the following requirements:
comply with product standard EN 1856-2;
its cross-section must be of constant diameter and no less than that of the appliance outlet, from the firebox outlet up to the
connection in the flue;
the horizontal section must be as short as possible and extend no more than 4 metres;
the horizontal sections must have a minimum upward slope of 3%;
changes of direction must have an angle no greater than 90° and be easy to inspect
the number of changes of direction, including that for entry into the flue, and exclusion of the T in the event of a side or rear
outlet, must not exceed 3;
it must be insulated if it passes outside the installation room
it must not in any case cross rooms in which it is forbidden to install combustion appliances.
the use of flexible metal and fibre cement or aluminium hoses is forbidden;
In any case, smoke ducts must be sealed against combustion products and any condensation. For this reason, it is recommended
to use pipes with silicone gaskets or similar sealing devices that withstand the operating temperatures of the appliance (e.g. T200
P1) and that by removing the gaskets, are still T400 N1 G certified.
SYSTEM TYPE Ø80 mm PIPE Ø100 mm PIPE
Minimum vertical length 1,5 mt 2 mt
Maximum length (with 1 union) 6,5 mt 10 mt
Maximum length (with 3 unions) 4,5 mt 8 mt
Maximum number of unions 3 3
Level section (minimum inclination 3%) 4 mt 4 mt
Installation at a height above 1200 m a.s.l. NO Obligatory
3.4 FLUE CHIMNEY OR PIPED DUCT
When creating the flue, in particular comply with the following requirements:
comply with the applicable product standard (EN 1856, EN 1857 EN 1457, EN 1806, EN 13063..);
be made with suitable materials to ensure resistance to normal mechanical, chemical, thermal stresses and have adequate
thermal insulation in order to limit the formation of condensate;
have a predominantly vertical configuration and be free of choke points along its entire length;
be correctly spaced by air gaps and isolated from combustible materials;
the flue inside the house must still be insulated and can be inserted in an air shaft provided it complies with the regulations
for piping;
the smoke duct must be connected to the flue by means of a Tee fitting with an inspectable collection chamber for the collec-
tion of soot and any condensate.
where the sizing provides for wet operation, a suitable condensate collection and siphon discharge system must be set up.
We recommend checking the data plates of the flue for the safety distances that must be observed
in the presence of combustible materials and, if necessary, the type of insulating material to be
used.
It is forbidden to connect the stove to a collective or shared flue with other combustion appliances
or with hood outlets.
It is forbidden to use the direct drain on the wall or towards indoor spaces and any other form of
drain not provided for by the regulation in force in the country of installation.
5


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Cadel Tabla at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Cadel Tabla in the language / languages: English as an attachment in your email.

The manual is 2.68 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Cadel Tabla

Cadel Tabla User Manual - English - 36 pages

Cadel Tabla User Manual - Dutch - 35 pages

Cadel Tabla User Manual - French - 35 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info