IDRO PRINCE
3
12-16-23-23 H
2
O - IDRO PRINCE 30-30 H
2
O - AQUOS
3
16-23-23 H
2
O - IDRON 16-22 AIRTIGHT - MIRA 16-22 -
TESIS 16-23
AIRTIGHT - HIDROFIRE 22.8
11
min.3,5 metri
AT
(A)
AP
(B)
Fig. 3 - Flue
3.7 TECHNICAL FEATURES
Have a qualified technician check flue efficiency.
The flue must be airtight, vertical without constrictions, made with materials that are resistant to smoke and condensate, thermal-
ly insulated, and suited to resist normal mechanical stresses over time (we recommend circular section insulated twin wall chim-
neys in A/316 or refractory material). It must be externally insulated to prevent condensation and to reduce the smoke cooling
effect. It must not be near combustible or highly flammable materials with an air or insulating material gap: check the chimney
distance indicated by the manufacturer according to EN 1443. The chimney opening must be in the same room in which the ap-
pliance is installed or, at most, in an adjacent room and must have under the opening a soot and condensate collection chamber
that can be accessed via an airtight metal door.
A
B
C
D
E
Fig. 4 - Flat roof
LEGEND Fig. 4
A 0.50 metres
B distance > 2 metres
C distance < 2 metres
D 0.50 metres
E technical volume
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Cadel MIRA 22 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Cadel MIRA 22 in the language / languages: English as an attachment in your email.

The manual is 2,7 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Cadel MIRA 22

Cadel MIRA 22 User Manual - German - 76 pages

Cadel MIRA 22 User Manual - Dutch - 72 pages

Cadel MIRA 22 User Manual - French - 72 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info