696326
14
Zoom out
Zoom in
Previous page
1/44
Next page
11
KOOK 60 4.0 - KOOK 67 4.0 - KOOK 70 4.0 - KOOK 80 - KOOK 87 - KOOK 90 4.0
EN
SYSTEM TYPE Ø150 mm PIPE Ø240 mm PIPE
Maximum number of unions 3 3
Level section (minimum inclination 3%) 2 mt 2 mt
Installation at a height above 1200 m a.s.l. NO Obligatory
Use a specic plate pipe for stoves.
It is forbidden to use metal, bre cement or aluminium exible pipes.
For change of direction it is obligatory always to use a T-union (or a curve not with right angle) with inspection
plug which enables an easy periodic cleaning of the pipes.
Please assure you that after the cleaning the inspection plugs are sealed with its efcient gasket.
It is forbidden to connect more appliances to the same fume conduit.
It is forbidden to convey in the same fume conduit exhausts from overhanging cooker hoods.
It is forbidden to exhaust ue gases directly from the wall towards the outside and closed spaces also at open
top.
It is forbidden to connect any other appliance (wood stoves, cooker hoods, boilers, etc...).
The fume conduit must be placed at a distance of minimum 500 mm from ammable or heat-susceptible
components.
The fume conduit must be connected with stove exhaust in a xed and tight manner, and if required with the
insertion of a damper (see FEATURES page 35).
It is prohibited to connect more than one wood/pellet (*) or any other type of appliance (vent cowling...) to the
same ue.
(*) unless there are national derogations (for instance in Germany), which under suitable conditions allow for
the installation of several appliances in the same replace. In any case, strictly follow the product/installation
requirements of the relative regulations/legislation in force in that country.
9.11 EXAMPLES OF CORRECT INSTALLATION
Fig. 9 - Example 1
LEGEND Fig. 9 page 11
1 Insulating material
2 Exhaust stub pipe
3 Inspection plug
4 Minimum safety distance = 0,5 mt
5 Damper
Chimney ue installation Ø150 mm with an enlarged drilling for pipe transit.
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Cadel KOOK 87V at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Cadel KOOK 87V in the language / languages: English as an attachment in your email.

The manual is 27,66 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Cadel KOOK 87V

Cadel KOOK 87V Usermanual and installation guide - German - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info