696354
8
Zoom out
Zoom in
Previous page
1/35
Next page
GRACE
3
- SPIRIT
3
- MADISON - TABLA - ROXY - ATRIUM
8
SYSTEM TYPE Ø80 mm PIPE Ø100 mm PIPE
Minimum vertical length 1,5 mt 2 mt
Maximum length (with 1 union) 6,5 mt 10 mt
Maximum length (with 3 unions) 4,5 mt 8 mt
Maximum number of unions 3 3
Level section (minimum inclination 3%) 2 mt 2 mt
Installation at a height above 1200 m a.s.l. NO Obligatory
Use a plate pipe for stoves of Ø80 mm or Ø100 mm depending on the type of system and with silicone gaskets.
It is forbidden to use metal, fibre cement or aluminium flexible pipes.
For change of direction it is obligatory always to use a union (with angle > 90°) with inspection plug which enables an easy
periodic cleaning of the pipes.
Please assure you that after the cleaning the inspection plugs are sealed with its efficient gasket.
It is forbidden to exhaust flue gases directly from the wall towards the outside and closed spaces also at open top.
The fume conduit must be placed at a distance of minimum 500 mm from flammable or heat-susceptible components.
It is prohibited to connect more than one wood/pellet (*) or any other type of appliance (vent cowling...) to the same flue.
(*) unless there are national derogations (for instance in Germany), which under suitable conditions allow for the installation of
several appliances in the same fireplace. In any case, strictly follow the product/installation requirements of the relative regulations/
legislation in force in that country.
3.9 EXAMPLES OF CORRECT INSTALLATION
Fig. 6 - Example 1
LEGEND Fig. 6
1 Insulating material
2 Reduction from Ø100 to Ø80 mm
3 Inspection plug
4 Minimum safety distance = 0,5 mt
Chimney flue installation Ø100/120 mm with an enlarged drilling for pipe transit.
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Cadel ATRIUM - 2019 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Cadel ATRIUM - 2019 in the language / languages: English as an attachment in your email.

The manual is 5,14 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Cadel ATRIUM - 2019

Cadel ATRIUM - 2019 Installation Guide - German - 35 pages

Cadel ATRIUM - 2019 Installation Guide - Dutch - 35 pages

Cadel ATRIUM - 2019 Installation Guide - French - 35 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info