AQUOS - IBIS - IDRON
EN
LEGEND
1 Windproof
2 Flue
3 Inspection
Use adequate instruments to verify that there is a minimum draught of 5 Pa.
Set-up an inspection hole at the bottom of the chimney to perform periodic checks and
cleaning, which must be done annually.
The connection to the chimney must be sealed and the ttings and pipes recommended
by us must be used (CE marked in accordance with EN1856-2 with the minimum requisites:
T200 and P1).
You must ensure that a windproof chimneypot is installed in accordance with the regulations
in force.
This type of connection guarantees smoke expulsion even in the event of a temporary
power cut.
5.7 OPERATING PROBLEMS RELATED TO DRAUGHT DEFECTS IN THE CHIMNEY
Among all the weather and geographical conditions that affect chimney operation (rain, fog, snow, altitude
a.s.l., exposure to sunlight, orientation to the cardinal points, etc.), the wind is certainly the most determinant.
In fact, besides the thermal depression caused by the difference in temperature between inside and outside
the chimney, there is another type of depression (or overpressure): dynamic pressure caused by the wind. An
updraft always increases depression and therefore the draught. A horizontal wind increases depression provided
the chimneypot has been installed properly. A downdraft always decreases depression, at times inverting it.
Fig. 4 - Example of depression
LEGEND
A Less favourable points
B Most favourable position
Besides the direction and force of the wind, the position of the chimney and the chimneypot with respect to the
roof of the building and the surrounding landscape is also important.
The wind also affects chimney operation indirectly by creating overpressure and depression zones within the
building as well as outside. An internal overpressure can be created in rooms that are directly exposed to the
wind (2), which can enhance the draught in stoves and replaces, however, it can be counteracted by the
external overpressure if the chimneypot is situated on the side exposed to the wind (1). On the other hand, a
dynamic depression can be created in rooms that are opposite the wind direction (3), which competes with the
natural thermal depression generated by the chimney, however, this can be compensated for (sometimes) by
placing the smoke duct opposite the wind direction (4).
IMPORTANT!
The operation of the pellet product is signicantly affected by the chimney layout and
position.
Hazardous conditions can only be resolved by qualied personnel setting the product
appropriately.
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Cadel Aquos 22 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Cadel Aquos 22 in the language / languages: English as an attachment in your email.

The manual is 6,26 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Cadel Aquos 22

Cadel Aquos 22 Usermanual and installation guide - German - 56 pages

Cadel Aquos 22 Usermanual and installation guide - Dutch - 56 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info