6 Installation instructions 0020246836_02
Appendix
A Detecting and eliminating faults
Fault Possible cause Remedy
No flow rate at the water
tap
1. The cold-water isolation valve is closed.
2. The main filter is blocked.
3. The pressure reducer is not installed correctly.
1. Check and open the cold-water isolation valve.
2. Close the cold-water isolation valve, and clean
the filter and the pressure reducer.
3. Check whether the pressure reducer has been
installed correctly.
Low flow rate and pres-
sure at a water tap
1. The filter in the cold water pipe is clogged. 1. Close the cold-water isolation valve, and clean
the pressure reducer filter.
Water from the water tap
is cold
1. The cylinder was not started up.
2. The cold-water isolation valve is not fully open.
3. The heat generator is not operating.
4. The thermal cut-out for a system component
has been triggered.
5. The 2-port motorised valve is defective.
6. The immersion heater is defective.
1. Open all of the relevant valves.
2. Check the thermostat or the room thermostat
and, if required, set this.
3. Check the heat generator to see if a fault code
is present.
4. Check and initialise the cylinder.
5. Check the connections for the 2-port motorised
valve.
Domestic hot water
temperature at the water
tap too high
1. The thermostat is set too high.
2. The thermostatic valve is not present or is
defective.
1. Check the target temperature. It must be
between 60 and 65 °C.
2. Install a mixer tap.
3. Check the cabling. Repair the cable.
4. Reduce the temperature of the thermostat to
60 °C.
5. Replace the thermostatic valve.
Irregular domestic hot
water output at the water
tap
1. The expansion vessel is defective.
2. The thermal cut-out for a system component
has been triggered (thermal control).
1. Compare the temperature between the con-
trols. The maximum temperature has priority.
2. If required, adjust the pre-charge pressure.
3. Interrupt the power supply to the product and
the heat generator. Check the thermal cut-outs
for the system components and replace these
in the event of a defect.
B Inspection and maintenance work Overview
The table below lists the manufacturer requirements with respect to minimum inspection and maintenance intervals. If na-
tional regulations and directives require shorter inspection and maintenance intervals, you should observe these instead of
the intervals listed.
# Maintenance work Interval
1 Check the connections for tightness (visual inspection). Annually
2 Check the temperature and pressure relief valve (by actuating it) Annually
3 Check the pressure in the expansion vessel (annual manometer). Annually
4 Check the tightness of the flange in the cleaning eye (visual inspection) Annually
5 Check the state of wear of the magnesium protection anode Annually
6 Clean the cylinder Annually
7 Check the contacts of the external current anode for corrosion Annually
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bulex FE 400 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bulex FE 400 in the language / languages: English, German, Dutch, French, Italian, Polish, Portuguese, Spanish as an attachment in your email.

The manual is 3,22 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info