SSB 6720818454 (2016/02) US
Applications | 53
(*) NOTICE: The maximum amp load for each pump is 1 A
when 2 or 3 pumps are connected. For this reason, if the
power consumption of each pump is higher than 84 watt,
use a relay as shown in gure.
If just one pump is connected, the maximum amp load
of this single pump is 2 A. For this reason if the power
consumption of the pump is higher than 168 watt, use a
relay as shown in Fig. 81.
The low voltage connections for “Primary boiler” are:
Terminal Number. Device
1-2 Cascade link
7-8 Outdoor air sensor (optional)
9-10 DHW tank sensor or Tank Thermostat (Aquastat)
11-12 Room thermostat
13-14 Supply sensor
The low voltage connections for “Secondary boiler” are:
Terminal Number. Device
1-2 Cascade link
The high voltage connections for “Primary boiler” are:
Terminal Number. Device
101-102-103 Boiler pump
104-105-106 CH pump
107-108-109 DHW tank pump
The high voltage connections for “Secondary boiler” are:
Terminal Number. Device
101-102-103 Boiler pump
8.3.1 Settings
Set the parameters as indicated in the following table (for the parameter
list see section “5.5 Parameters list”):
No. Description Value Comment
1
Central Heating
Mode
0 Outdoor air sensor not present
1
Outdoor air sensor present. Reset
curve activate
2 Mod Pump Mode 2 Enabled CH pump and DHW pump
35 DHW mode
0 No indirect sanitary water installed
1 Indirect sanitary water with sensor
2
Indirect sanitary water with tank
thermostat
If CH mode is set to 1 and an outdoor air sensor is present, set the reset
curve parameter as follows (to set these values see also section “5.6
Outdoor reset”):
No. Description Value (°F)
19 Design Supply Temp 180
20 Design Outdoor Temp 25
21 Baseline Supply Temp 104
22 Baseline Outdoor Temp 70
23 Design Supply Min Limit 40
24 Design Supply Max Limit 180
25 Warm Weather Shutdn 68
53


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus SSB512 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus SSB512 in the language / languages: English as an attachment in your email.

The manual is 9,92 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Buderus SSB512

Buderus SSB512 Installation Guide - French - 68 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info